ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
75
7.1
Power Meter Setting
On the “Power Meter Setting” page, it allows to set up the settings of the
Modbus RTU and Modbus TCP power meters that are connected to the
PMC/PMD. The Power Meter Setting page is shown as below:
Figure7-2 :
Power Meter Setting Page
On the Power Meter Setting page, a list for all power meters connected to
the PMC/PMD will be displayed. Please follow the following sections to
perform settings for Modbus RTU and Modbus TCP power meters. After all
settings are completed, click “Save” button to save the changes.
Please note:
1.
PMC/PMD provides 2 COM Port(RS-485) interface that allows
connections to Modbus RTU power meters.
2.
PMC/PMD provides LAN interface that allows connections to Modbus
TCP power meters. For more detailed information about LAN settings
please refer to “
3.
One PMC/PMD allows connections to at most 24 ICP DAS Modbus
TCP/RTU power meters (with maximum 16 Modbus TCP Power
Meters), and 8 Modbus I/O modules.
Each RS-485 interface (with Modbus RTU Master) can connect to
Max. 16 power meters.
Support at most 4 ICP DAS PM-4324 series Power Meters.