ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
113
If users select “32-bit Signed Long”, “32-bit Unsigned Long”,
or “32-bit Floating Point”, the option “Inverse(Big Endian)”
will appear. Enable “Inverse(Big Endian)” to receive the data in
big endian format correctly.
After finishing the “Start Address”, “Data Number”, and “Type”
setting, click on “Add” button. A new Input Register address
block will be added to the Modbus address mapping table
(shown as below). All added address blocks will be located in
sequences staring from the Starting Address (The address
number on the first column of the “Local Address” indicates the
local Modbus address of PMC/PMD to keep the Input Register
data.).
Figure 7-48 shows an example about Input Register setting for a
Modbus RTU module. The starting Modbus address of the Input
Register block is 30010(30000 + 10), it requires to set 3
continuous Input Register data in the setting, and the data type
is “32-bit Floating Point”. So that these retrieved Input Register
data will be kept in PMC/PMD Address 30300, 30302, and
30304.
Figure7-48 :
Input Register Setting Example for Modbus RTU Module
To modify the starting address or quantity setting, please click
Содержание PMC-523 Series
Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...