Q4: How to write data to output channels on a Modbus RTU slave device?
A4:
Step 1:
Edit the polling definition for the output channels with read function code in the
config.csv file. (For example, use 01 to read DO channels, 03 to read AO channels)
Step 2:
Import the config.csv file into the MDC-700, wait the MDC-700 reboot in 5 seconds, and
then check the addresses for the local registers mapped to the output channels.
Step 3:
Write data with corresponding function code (05/06/15/16) on your Modbus master
device to the local registers mapped for the output channels, the MDC-700 will process
writing operations to the slave devices.