Getting Started:
PAC-5007/5107/5207/5307 Ver. 1.1, 12/2011 ICP DAS
.
3-13
Set COM2 or COM3 as Modbus RTU Slave:
7.
Type
"isa5307 *x=PB"
to set the baud rate of COM2/3 and as a Modbus RTU Slave
port.
"P" means the COM Port number. (P = 2 or 3)
,
"B" means the baud rate. (B = 0 ~ 9)
1=2400,
2=4800,
3=9600,
4=19200,
5=38400,
6=57600,
7=115200,
8=300,
9=600,
0=1200
Set COM2/3 baud rate and define it as a Modbus RTU
"PB" =
2
0 ~
2
9, set COM
2
to Modbus Slave Port
"PB" =
3
0 ~
3
9, set COM
3
to Modbus Slave Port
Ex: Set COM2 as Modbus RTU Slave Port, baud rate is 19200.
8.
Exit the "7188xw" screen; else the COM1/COM2 is always in use.
9.
Switch the “Init*” to “OFF” then power it up.
Recovery the COM2/COM3 Setting:
If you want to set COM2/COM3 as Non-Modbus RTU Slave Port, please type
"isa5307
*x=f"
to release it.
Please type the instruction according to
the controller model. (Ex. isa
5307
*x=24)