Getting Started: I-8437-80/8837-80/8417/8817, Jul 2020 V2.0 63
Step 2: Initialize I/O module
The factory settings of I/O modules are listed in the first table. If the current settings of the
module are unknown, only initialize the module to reset the settings as listed in the second
table.
The factory settings:
I/O Module
I-7000
M-7000
I-87K series
Address
1
1
1
Baud rate
9600
9600
115200
Checksum
Disabled
Not defined
Disabled
Protocol
DCON Protocol
Modbus Protocol
DCON Protocol
The initial settings:
o
To initialize an I-7000 module, set the DIP switch to INIT (or connect the INIT* pin to the GND
pin) and power on the module. This status also called “INIT mode”.
o
To initialize an I-87K module, set the DIP switch on the I-87K4/5/8/9. For example, adjust the
Dip-2 to “ON” and restart the I-87Kn to initialize the module on slot2.
I/O Module
7000 series (I-7000 and M-7000)
I-87K series
Address
0
0
Baud rate
9600
115200
Checksum
Disabled
Disabled
Protocol
DCON Protocol
DCON Protocol
Step 3: Select COM Port and Baud Rate to search
Click Windows “Start” and point to “programs”, “ICPDAS”, and “DCON_Utility”. Then, click
DCON_Utility
to execute the software.
1.
Click the
“
COM Port
”
menu to select the COM Port and Baud Rate to search. You can select
multiple Baud Rate, Protocol, or Checksum if you do not know the module’s setting, but it
will spend more time searching the module. After selection, click
“
OK
”
.