Getting Started: I-8437-80/8837-80/8417/8817, Jul 2020 V2.0 62
3.14
Setting I-7000 and I-87K Remote I/O by DCON Utility
PAC can link up to 64 pcs ICP DAS's I-7000 and I-87K series remote I/O modules.
Important Notice:
Before the I-7000 or I-87K I/O modules are connected to the PAC, the user needs to set the
unique address (NET-ID) and the same baud rate with the PAC for each I/O module by using
DCON Utility.
DCON Utility is a toolkit that can be used to search, configure, and test the I/O modules.
Visit to the website to download the software and the user manual:
https://www.icpdas.com/en/product/guide+SUtilityDCON__Utility__Pro
NOTE:
1.
Make sure the hardware connection is correct.
2.
Configure I-87K I/O modules with
3.
Search and configure the modules one by one.
4.
Set the module as the INIT mode and power it up.
Step 1: Hardware connection
1.
The power supply must be DC power b10 ~ +30 V.
2.
The figure below shows the way to connect the I-87K4 and I-87K module. Note that only
connect one module for each time.
NOTE:
For using I-87K4 I/O module, you have to prepare an I-7520R (RS-232 to RS-485) converter. Also,
refer to
” for more information about wiring the module.
I-87Kn User Manual:
http://www.icpdas.com/en/download/show.php?num=408
I-7000 User Manual:
http://www.icpdas.com/en/download/show.php?num=1860
Note:
In INIT mode, the setting of I/O module will be initialized.
(Initialize I-87K)
1.
DIP-1= ON
2.
Power on
(Initialize I-7000)
Init
Normal
Power on