ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
1/2
2019.12
Thermocouple Type
Type Code
Thermocouple Type
Temperature Range
0E
J
-210 to +760°C
0F
K
-270 to +1372°C
10
T
-270 to +400°C
11
E
-270 to +1000°C
12
R
0 to +1768°C
13
S
0 to +1768°C
14
B
0 to +1820°C
15
N
-270 to +1300°C
16
C
0 to +2320°C
17
L
-200 to +800°C
18
M
-200 to +100°C
19
L2
DIN43710
-200 to +900°C
Features
I-7018
±120 V
DC
Overvoltage Protection
8-channel Diff erential or 6-channel Diff erential and
2-channel Single-ended Analog Input
I-7018R and M-7018R
Overvoltage Protection can be up to 240 V
rms
8-channel Diff erential Analog Input
Current, Voltage or Thermocouple Input
3000 V
DC
Intra-module Isolation
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
I-7018(R)
M-7018(R)
The I-7018/M-7018 is an 8-channel Analog Input module that provides
current and voltage input, as well as thermocouple input. The I-7018R/
M-7018R is an upgraded version of the I-7018/M-7018 that includes an
extremely high-quality protection mechanism where the overvoltage
protection can be as high as 240 Vrms. The I-7018R/M-7018R is more
suitable for critically harsh environments, and the newly-added open
thermocouple detection feature makes the I-7018R/M-7018R more attractive
than ever. The I-7018/M-7018/I-7018R/M-7018R also features 4 kV ESD
protection and 3000 V
DC
intra-module isolation. The specifications for the
M-7018 and M-7018R are the same as the I-7018 and I-7018R, but provide
additional support for the Modbus RTU protocol as well as the DCON
protocol.
Model
I-7018
I-7018R
M-7018
M-7018R
Communication
Interface
RS-485
Bias Resistor
No (Usually supplied by the RS-485 Master. Alternatively,
add a tM-SG4 or SG-785.)
Format
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate
1200 to 115200 bps
Protocol
DCON
Modbus RTU, DCON
Dual Watchdog
Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator
Yes, 1 as Power/Communication Indicator
I/O LED Indicators
-
7-segment LED Display
-
Isolation
Intra-module Isolation,
Field-to-Logic
3000 V
DC
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
EFT (IEC 61000-4-4)
±4 kV to Power
Surge (IEC 61000-4-5)
±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range
+10 ~ +30 V
DC
Consumption
1.0 W
Mechanical
Dimensions (L x W x H)
123 mm x 72 mm x 35 mm
Installation
DIN-Rail or Wall Mounting
Environment
Operating Temperature
-25 to +75°C
Storage Temperature
-40 to +85°C
Humidity
10 to 95% RH, Non-condensing
Model
I-7018
I-7018R M-7018
M-7018R
Analog Input
Channels
6 Diff erential
and 2
Single-ended,
or 8 Diff erential
8
Diff erential
6 Diff erential
and 2
Single-ended,
or 8 Diff erential
8
Diff erential
Wiring
Diff erential
Sensor
Types
Thermocouple J, K, T, E, R, S, B, N, C
Voltage
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA
(requires an optional external 125 Ω resistor)
Resolution
16-bit
Accuracy
0.1% of FSR
Sampling Rate
10 Hz (Total)
Input Impedance
> 400 kΩ
Common Voltage Protection 25 V
DC
200 V
DC
25 V
DC
200 V
DC
Individual Channel
Confi guration
-
Yes *Note2 -
Yes *Note3
Overvoltage Protection
±120 V
DC
240 V
rms
±120 V
DC
240 V
rms
Open Wire Detection
(for thermocouple only)
-
Yes
-
Yes
Temperature Outputs
Consistency
-
Stable Temperature Output
in the Field
-
8-channel Analog Input Module
Introduction
Applications
System Specifi cations
I/O Specifi cations
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Note 1:
For highly-accurate thermocouple measurement, ICP DAS recommends selecting
the I-7018Z/I-7019Z module,which features automatic cold-junction compensation
for each channel, ensuring consistent and stable temperature output.
Note 2:
Firmware version B4.2 or later.
Note 3:
Firmware version B4.5 or later.