M-7084 User Manual, Rev. A1.3 7PH-013-A13
68
2.20 $AAI
Description:
Reads the INIT status.
Syntax:
$AAI[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
I
Command to read the INIT status
Response:
Valid Response:
!AAS[CHKSUM](CR)
Invalid Response:
?AA[CHKSUM](CR)
!
Delimiter character for a valid response
?
Delimiter character for an invalid response
AA
Address of the responding module (00 to FF)
S
INIT status:
0= the INIT pin is shorted to GND.
1= the INIT pin is not shorted to GND.
2= Update CJC temperature once only.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.