I-2533CS-FD ( CAN/CAN FD to Single-mode Fiber Bridge ) User Manual (version 1.1.0)
Page: 36
Copyright © 2020 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
5. Firmware Upgrade
Please refer to the following steps to upgrade the firmware of I-2533CS-FD module.
Step 1: Power off the I-2533CS-FD.
Step 2: Set the I-2533CS-FD’s pin 10 of 10-pin dip switch to ‘ON’ position.
10-pin dip switch
Pin
Switch
Function
Description
10
Firmware
upgrade
mode
ON:
Into firmware
upgrade mode.
OFF:
Into normal
operating mode.
Step 3: Power on the I-2533CS-FD, the CAN_Err, CAN_Tx, CAN_Rx, FB_Err LEDs will
flash per 500 milliseconds.
Step 4: Connect the PC available USB port with the
USB port of the I-2533CS-FD. Users can find the communication cable
(CA-USB10) in the product box.
Figure 5-1-1 Wire connection of the USB