Programming
Programming Frequency Pulse Relay Output
STEPS
DISPLAY
OPERATION
Home Screen
Factory Default: Lk = 10
Otherwise meter will enter
Lockout Mode*
Press /
STR
to change
Press to save
Ut.G = Gallons (Factory default)
Ut.L = Liters | Ut.KL = Kiloliters
Press to change
Press to save
Enter K Factor Value
Refer to Page 6 for K-Factor Values
Factory Default — 4mA = 0, 20mA = 100**
**This can be change to suit application
STEPS
DISPLAY
OPERATION
Home Screen
CV -
Program Value of (Flow Rate) Pulse (NPN) Output
Preset Value of Flow Rate
Change to a Value that meets your Flow Rate Pulse Output
SV -
CV > SV ▶ Flow Rate Pulse Output ON
CV < SV ▶ Flow Rate Pulse Output OFF
CV -
Program Value of Flow Totalizer Pulse (NPN) Output
SV: Preset Value of Flow Total
SV -
CV > SV ▶ Flow Rate Pulse Output ON
2000 Default
can be changed to desired value. Refer to "Programming
OP2 Output" for totalizer options
Flow Totalizer Pulse
- (Step #2 - Next)
Transmitter Range
5
▶
K Factor
4
▶
Pasword
Flow Rate Pulse Output
2
2
Select/Save/Continue
Move selection left
Change digit value
▶
▶
Units of Flow
Flow Total Pulse Output
3
3
▶
▶
Press and Hold
SET
Press and Hold
SET
1
1
▶
▶
STR
TIF Series
Multi-Function Batching Paddle Wheel Flow Meter
6
23-0069
+
🕓
3 Sec.
+
🕓
3 Sec.