Installation, Operation & Application Guide

For more information on our complete range of 
American-made products – plus wiring diagrams, 
troubleshooting tips and more, visit us at  
www.icmcontrols.com

SC700LV

Non-Programmable Fan Coil Thermostat

Specifications

Important Safety Information

•  Always turn off the thermostat before installing, removing, cleaning, or 

servicing; turn off the power at the main power source by unscrewing fuse 
or switching off circuit breaker 

•  Do not install on voltages higher than 30 VAC
•  All wiring must conform to local and national building and electrical codes 

and ordinances

•  While cleaning, do not get soap directly on thermostat switches or slide 

bar area; only use a damp cloth with a mild soap to wipe outside of 
thermostat cover

To Remove Existing Thermostat

ELECTRICAL SHOCK HAZARD

 – 

Turn off power at the main 

service panel by removing the fuse or switching the appropriate 
circuit breaker to the OFF position before removing the existing 
thermostat.

1.  Turn off power to the heating system by removing the fuse or switching 

the appropriate circuit breaker off.

2.  Remove cover of old thermostat. This should expose the wires.
3.  Label the existing wires with the enclosed wire labels before removing 

wires.

4.  After labeling wires, remove wires from wire terminals.
5.  Remove existing thermostat base from wall.
6.  Refer to the following section for instructions on how to install this 

thermostat.

To Install Thermostat

ELECTRICAL SHOCK HAZARD

 – Turn off power at the main 

service panel by removing the fuse or switching the appropriate 
circuit breaker to the OFF position before removing the existing 
thermostat.

 

IMPORTANT:

 

Thermostat installation must conform to local and 
national building and electrical codes and ordinances. 

 

 

Note:

 

Mount the thermostat about five feet above the floor. Do not 
mount the thermostat on an outside wall, in direct sunlight, 
behind a door, or in an area affected by a vent or duct.

1.  Turn off power to the heating and cooling system by removing the fuse or 

switching off the appropriate circuit breaker. 

2.  Move the 

ON/OFF

 switch to 

OFF

.

3.  Move 

Fan

 switch to either 

HI

/

MED/LO

.

4.  To remove cover, turn set screw on bottom of thermostat clockwise.
5.  Put thermostat base against the wall where you plan to mount it (be sure 

wires will feed through the wire opening in the base of the thermostat).

6.  Mark the placement of the mounting holes.
7.  Set thermostat base and cover away from working area.
8.  Using a 3/16” drill bit, drill holes in the places you have marked for 

mounting.

9.  Use a hammer to tap supplied anchors into mounting holes.
10.  Align thermostat base with mounting holes and feed the control wires 

through wire opening.

11.  Use supplied screws to mount thermostat base to wall.
 

CAUTION!

Do not overtighten. May cause case to distort and risk 
exposure to voltage. 

Be sure exposed portion of wires 

does not touch other wires.

12.  Tighten screws on terminal block. Gently tug wire to be sure of proper 

connection. Double check that each wire is connected to the proper 
terminal.

13.  Replace cover on thermostat by snapping it in place.
14.  Turn set screw on side of cover counter-clockwise until cover can not 

be removed.

15.  Turn on power to the system at the main service panel.

Parts Diagrams (SC700)

•  18-30 VAC
•  Auto Changeover
•  Controls Single Stage Heating/

Cooling Systems

•  3-speed fan control
•  Easy slide bar temperature 

adjustment

•  Mercury-Free, Environmentally Safe

Input:

• 

Voltage:

 18-30 VAC

Output:

Fan and System Switches

Voltage 

Rating

Inductive

Pilot
Duty

Heat/Cool  

Outputs

FLA

LRA

24 VAC

N/A

N/A

24 VA

10 VA

• 

Temperature control ranges: 

50°F to 90°F   

Accuracy:

 ± 2°F

• 

Differential range: 

Fixed 2°F

• 

Deadband: 

Fixed 4°F

• 

System configurations:

 Single-stage heat, single-stage cool

Specifications

Package includes:

 

SC700

 non-programmable thermostat on base, 

thermostat cover, wiring labels, screws and wall 
anchors, Installation, Operation and Application Guide.

Tools required for installation:

 Drill with 3/16” bit, hammer, screwdriver 

and hex wrench (included in package)

SC700

NOTE:

 

Switch caps must be installed with point in this 
position to insure proper operation.

TEMP. IND. AND REG. EQUIP.

4PC1