ICM Controls ICM600 Скачать руководство пользователя страница 1

ICM600/ICM601

Lead Lag Controller

Microprocessor controlled regulation for 

one or two heating/cooling systems to 

provide a constant temperature.

Specifications

Caution

Installation of the ICM600/ICM601 shall be performed by trained 

technicians only. Adhere to all local and national electric codes. 

Disconnect all power to the system before making any connections

.

ELECTRICAL
Input

• 

Nominal Voltage:

 18 to 30 VAC

• 

Frequency:

 50 to 60 Hz

Output

• 

Type:

 Triac

• 

Number:

 Four (4)

• 

Rating:

 2 amps per output @ nom. 24 VAC

OPERATIONAL
Heat/Cool Staging

 

• 

First Stage Heat (H1):

 Deadband setting above thermostat setpoint (C1)

• 

Second Stage Heat (H2):

 2°F above H1

• 

First Stage Cool (C1):

 Equal to the thermostat setpoint 

• 

Second Stage Cool (C2):

 2°F below C1

Deadband

• 

Adjustable:

 2°F to 20°F

Anti-short Cycle Protection

• 

Stage 1:

 Three (3) minutes

• 

Stage 2:

 Four (4) minutes 

Setpoint

• 

Adjustable:

 55°F to 90°F 

Advance Sequencer

• 

Pin selectable:

 Alternates every 1, 3, 7, 14, or 28 days, or fixed

•  Manual 

ADVANCE

 pushbutton initializes sequence period

Mode Memory

•  On power loss, system “remembers” which mode it was in

Test Modes

•  Thermistor bypass calibration mode jumper
•  Accelerated test mode jumper

Call Lights (LEDs)

• 

Green LEDs:

 Call for COOL (C1 & C2)

• 

Red LEDs:

 Call for HEAT (H1 & H2)

Main steps for programming the Lead-Lag Controller:

 

1. Temperature Selection Pot

 

2. Deadband Pot 

 

3. Advance Sequencer

 

4. Advance (Override) Switch

 

5. Test Mode Jumper

1.  Temperature Selection Pot:

 

This selection pot is the temperature above which the cooling cycle 
begins. In cooling mode, the green “call for cool” indicator light - C1 (and 
C2 if second stage cooling is required) stays on. Each light corresponds 
to one stage of cooling. The temperature spacing between these lights is 
approximately 2°F. In heating mode, the red “call for heat” indicator lights, 
H1 and H2, operate similarly. The temperature spacing between cooling 
and heating modes is the deadband setting.

2.  Deadband Pot:

 

The deadband is the range where neither heating nor cooling is necessary. 
The deadband adjustment moves the heating setpoints in relation to 
the cooling setpoints. At its minimum position (counterclockwise) the 
deadband is 2°F. At its maximum position the deadband is 20°F. 

3.  Advance Sequencer:

 

For 2-stage alternating installations, the advance sequencer demands 
equal operating time from  
groups A and B. Select the time interval by placing a jumper over one 
of the jumper pair posts. The jumper labeled “0” disables the advance 
timing; use it when the controller is connected to a single heating/cooling 
group, or when alternating operation between two heater/cooler groups 
is not desired. In test mode (when the test mode jumper is installed), the 
advance times are accelerated (see the values shown in the Test Mode 
Advance Time Table). In normal mode (test mode jumper removed), 
advance times are in days as printed on the printed circuit board  
(i.e. 1, 3, 7, 14, 28). Setting the controller for 7 days is appropriate for most 
installations.

4.  Advance (Override) Switch:

 

The advance switch is a pushbutton switch provided to override the timing 
and instantaneously switch the lead group. The two red LEDs indicate 
which group will start first. The LED on the left is group A and the LED 
on the right is group B. Pressing the switch not only changes the lead 
group, but also restarts the anti-short cycle delay on make, and sets the 
main timer to zero. This feature can be used to reset the timer so the next 
advance time will be known.

5.  Test Mode Jumper:

 

The test mode provides for accelerated testing of the advance (override) 
function of the controller and the output delay on make times. When the 
test mode jumper is installed, the advance time conversion is from days to 
seconds. Accelerated anti-short cycle delay on make times are 1 second 
for stage one heating/cooling, and 4 seconds for stage two heating/
cooling. Test mode advance times are as specified in the table below.

Operation

TEST MODE ADVANCE TIME TABLE

Jumper Number

Advance Time (seconds)

0

• no advance •

1

1

3

3

7

7

14

14

28

28

For information on our complete range of American-made 

products — plus wiring diagrams, troubleshooting tips and 

more, visit us at 

www.icmcontrols.com

APPLICATION GUIDE

Отзывы: