Description

Ratings

Service Voltage (3-Phase) 120/240 VAC Delta High-Leg
Short Circuit Current 

Rating (SCCR)

200 kA

Nominal Discharge 

Current (In)

20 kA

SPD Type

Type 1 (Can also be used in Type 2 applications)

Surge Protection 

Technology

TFMOV

Protection Mode

3 for Delta configuration

VPR (Vpk)

VOLTS (V) 

MODE 

VPR (Vpk)

240/120 L-L  1200

 

L-N 700

 

H-L 1500

 

H-N 900

Maximum Continuous 

Operation Voltage (MCOV)

L-L: 300 VAC     L-N: 150 VAC      H-L: 450 VAC     

H-N: 300 VAC      

Input Power Frequency

50/60Hz

Diagnostics

Green LED indicates surge protection present

Enclosure Rating

NEMA/Type 4X water tight plastic enclosure for 

outdoor and indoor installation

Installation Point

Electrical panel/disconnect

Dimensions

4.3” X 4.1” X 2.3”

Operating Temperature

-40°F to 185°F (-40°C to 85°C)

Operating Humidity

Less than 85%, noncondensing

Operating Altitude

Less than 2000 meters

Agency Certification and 

Approvals

ANSI/UL1449 4th Edition Listed Device - cULus 

Listed

The ICM533 is a UL Listed Type 1 & 2 Surge Protective Device for Delta 

High-Leg 120/240 VAC Three Phase voltage configurations. When a surge 

occurs, the ICM533 will absorb the surge up to the limits expressed in 

the specifications section of this guide. The ICM533 incorporates thermal 

protection on the surge elements (TMOV’s) which allows for safe disabling 

of the surge elements when a surge exceeds the thermal limits of the 

device. The ICM533 has a status light on the control which identifies 

operational status when illuminated. The ICM533 can be installed as a  

Type 1 or Type 2 device for both indoor and outdoor applications. Suitable 

for use on a circuit capable of delivering not more than 200kA RMS 

symmetrical amperes, 240V maximum (Convient à des circuits produisant 

au plus 200kA RMS A eff.”, 240V maximum).

Periodically check the LED status on the SPD. If the Greenlight is OFF, 

the protection is no longer available and the SPD needs to be replaced 

immediately. 12 AWG stranded copper wire or larger required. Product 

contains no serviceable parts. This device features an internal protection 

that will disconnect the surge protective component at the end of its 

useful life but will maintain power to the load – now unprotected.

E347279

MAINTENANCE

MODE OF OPERATION

SPECIFICATIONS

The conductors used to connect the SPD shall not be any longer 
than necessary and shall avoid unnecessary bends.
1.  Turn off the main breaker and/or main power to the service 

disconnect.

2.  Verify your mains voltage and match that with ICM533 ratings.
3.  Remove the cover on service disconnect or the electrical panel.
4.  Mount the ICM533 through the 3/4” conduit connection of the 

electrical panel.

5.  Remove the retaining ring and washer on the ICM533.
6.  Feed the wires into the electrical panel or service disconnect.
7.  Re-secure the retaining ring and washer.
8.  Route the white wire to the neutral lug and secure.

Wiring Type 1 installation

•  Route the two black wires and one red wire to the appropriate L1, L2, 

and L3 connections before the breaker panel as seen in the wiring 
diagram for Type 1 installation and according to your local, state, and 
national electrical codes.   

 NOTE: The red wire attaches to the high-leg.

Wiring Type 2 installation
•  Route the two black wires and one red wire (L1, L2, and L3) to the 

individual breakers on the circuit breaker panel as seen in the wiring 
diagram for Type 2 installation and according to your local, state and 
national electrical codes.   

 NOTE: The red wire attaches to the high-leg.

 9. Reinstall cover on service disconnect or the electrical panel.

10. Restore power; Green LED should be on indicating full protection.

ELECTRICAL SHOCK HAZARD!

 – Before installing 

this unit, turn off power at the main service panel by 

removing the fuse or switching the appropriate circuit 

breaker to the OFF position.

•  WARNING — No Serviceable Parts  (Attention: Aucune pièce 

remplaçable ou reparable).

• WARNING — Shock hazard — 

Do not open (ATTENTION – RISQUE 

DE CHOC – NE PAS OUVRIR).

INSTALLATION, OPERATION & APPLICATION GUIDE

For more information on our complete range of American-made products – plus wiring 

diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com

ICM533

Surge Protective Device for 3-Phase Delta High-Leg 120/240 VAC

IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS

Limited lifetime 

product, up to a 3-year 

$10,000 connected 

equipment warranty

Please follow all State, Local and National electrical codes when 

installing this product. Installation should only be done by a licensed 

electrician for Type 1 devices or a licensed HVAC technician for Type 

2 devices.