Installation, Operation & Application Guide

For more information on our complete range of 

American-made products – plus wiring diagrams, 

troubleshooting tips and more,  

visit us at 

www.icmcontrols.com

ICM2813

Integrated Furnace Control Board

Features

• Controls the gas valve, inducer draft motor, circulating 

blower and hot surface ignitor

• Monitors system pressure and limit switches

• Microprocessor based precision

• Diagnostic LEDs aid in testing and troubleshooting

The ICM2813 is a form, fit, and functional replacement for the Lennox and White Rodgers boards shown in the cross reference 

section of this guide. The ICM2813 automated gas ignition control board monitors the ignition sequence including the inducer, 

pressure switch, hot surface igniter, gas valve, flame sense, and circulating blower while maintaining full safety circuit monitoring 

including the high limit switch, roll out switch and auxiliary limit switch circuits. Onboard diagnostics will indicate when a fault 

condition exists.

Introduction

Replaces

Lennox: 10M9301, 12L6901, 32M8801, 56L8401, 24L8501, 

63K8901, 97L4801, 100925-01, 100925-03, 

17W9201, 23W5101, 30W2501, 69M0801, 

69M1501, 83M00  

White-Rodgers: 50A65-120, 50A65-121, 50A62-120,  

50A62-121, 50A62-820, 21D83M-843, 

50A66-122, 50A66-123

Specifications

•  Electrical Rating @ 77°F (25°C)

•  Input Voltage: 18-30 VAC, 60 Hz 

 

•  Ignitor Current: 2.0 amp @ 80 VAC, 60 Hz (resistive)

•  Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC

•  Blower Relay: 14.5 FLA–25.0 LRA @ 120 VAC  

 

(Heat / Cool / Fan)

•  Gas Valve Relay: 1.5 amp @ 25 VAC, 60 Hz 0.6 pf

Environmental

•  Operating Temp Range: -40° to 176°F (-40° to 80°C) 

•  Humidity Range: 5 to 95% relative humidity  

 

(non-condensing)

Upon a call for heat, the thermostat will energize the W terminal with 24 VAC. With the heat call in place, the inducer fan and 

humidifier (optional) will be energized thus closing a pressure safety switch. The control will enter a 15 second inducer pre purge 

cycle. Upon verification of the pressure switch closure and completion of the 15 second inducer pre-purge, the hot surface igniter 

is energized. There is a 20 second igniter warm up period before energizing the gas valve. Once the gas valve is energized, 

gas flows into the burners where it is ignited by the hot surface igniter. Once the burners are on, the flame is sensed by a flame 

rectification circuit and flame sensor. There is a 4 second trial for ignition period where the control checks the flame signal and 

proves the flame. Once flame is established, there will be a 45 second heat ON delay before energizing the main blower. When 

the call for heat ends, the gas valve is de-energized, burners go off, flame is proven lost and there is a fixed 5 second inducer 

post purge to purge any residual exhaust gases from the system. Following the inducer post purge, the inducer and humidifier are 

turned off and subsequently the heat blower is turned off after the user selected off delay time expires. Upon a call for cooling, the 

Y terminal is energized with 24 VAC and a 2 second cool blower ON delay begins. After the ON delay expires, the EAC and cool 

blower outputs are energized. Once the call for cooling ends, there is a user selectable 2 second or 45 second cooling blower 

OFF delay to purge the residual cool air from the duct work. At the end of the OFF delay, the cool blower and EAC are turned off.

Mode of Operation

There is a 5 minute self healing recovery which occurs if the pressure switch is stuck open. The inducer will run for 150 seconds 

then enter a 5 minute self healing recovery. This cycle will repeat until the pressure switch closes.

There will be a 1 hour lock out if the flame is not established and proved within 5 successive attempts. After one hour in lockout, 

the control will reset automatically.

Lockout Features

Содержание ICM2813

Страница 1: ...nal will be energized thus closing a pressure safety switch The control will enter a 15 second inducer pre purge cycle Upon verification of the pressure switch closure and completion of the 15 second inducer pre purge the hot surface igniter is energized There is a 20 second igniter warm up period before energizing the gas valve Once the gas valve is energized gas flows into the burners where it i...

Страница 2: ...hich can cause dangerous operation 1 Turn thermostat to OFF position or set it to the lowest possible setting 2 Turn OFF electrical supply to furnace 3 Turn OFF gas supply to furnace 4 Remove furnace blower and control access doors 5 Remove control box cover CAUTION Failure to turn off gas and electric supplies can result in explosion fire death or personal injury 6 Disconnect thermostat wires and...

Страница 3: ...cription Trouble Shooting Tips ON Normal operation N A OFF Control board failure Check for proper input voltage and check the fuse if not resolved replace control 1 Ignition failure soft lockout Clean or replace the flame sensor check the igniter for proper operation input voltage check the transformer s common is grounded to earth ground 2 Pressure switch stuck closed Check for contaminated or de...

Страница 4: ...nsor P1 P2 Neutral P1 Plug Pin Out 1 High limit output 2 N A 3 24 VAC 4 N A 5 Rollout switch 1 6 24 VAC common 7 High limit input 8 Ground 9 Main valve common 10 Pressure switch 11 Rollout switch 2 12 Main valve P2 Plug Pin Out 1 Inducer Blower 2 Hot Surface Ignitor 3 Neutral 4 Neutral Chasis ground Earth ground PIN 11 PIN 10 PIN 9 PIN 7 PIN 8 PIN 5 PIN 6 PIN 3 PIN 4 PIN 1 PIN 2 Legend EAC Electro...