General information
19
Thermoregulator parametrization example
Push the enter key (4), field 2 to display the HSET variable and field 3 to display the variable parametrization (example: working
temperature hysteresis 2°C); to modify the variable push the up and down keys (5).
Attention: HSET hysteresis affects both above and below the Set Point; this means that, for example, if the desired Set Point
temperature is 110°C and hysteresis 2°C, the control at 2nd stage burner will be interrupted at 112°C and activated again at 108°C.
When the enter key (4) is pushed again, the system goes to the SP variable (example: working temperature 110°C, burner 2nd
stage control); to modify the variable push the up and down keys (5).
By doing it again, the system goes to the AL2 variable (example: limit temperature 120°C, burner ON-OFF), to modify the variable
push the up and down keys (5).
At last the system goes to the HAL2 variable (example: limit temperature hysteresis 2°C), to modify the variable push the up and
down keys (5).
Attention: HAL2 hysteresis only affects above the limit set; this means that, for example, if the desired temperature limit is 120°C
and hysteresis 2°C, the burner ON-OFF control will be interrupted at 122°C and activated again at 120°C.
At the end of the parametrization wait a few seconds, the thermoregulator goes automatically to normal visualization.
Message display front (Alarms)
1
Alarm output connected - Buzzer on electric panel enabled
2
Alarm indicator
3
Indication of several alarms - There is more than one alarm
4
Alarm/s indicator - Alarm indicator box, see the type below, if there are several alarms the display will display them alternately
every 4 seconds
5
Alarm silencing key - Press to mute the buzzer, when a new alarm appears it will switch back on automatically
6
Key to reset the alarms in the memory - If signal 2 is not on and the display is flashing, alarm/s in the memory but not present,
the button can be used to clear it/them.
Alarm indications
A.01 = (Minimum or maximum) pressure alarm, check the system pressure, the settings of the loading system and of the expansion
system
A.02 = High temperature alarm, check the flow water temperature and the parametrization of the control thermoregulator
A.03 = Safety circuit alarm, indicates a fault inside the control panel
A.04 = Burner shut off alarm, indicates an incorrect operation of the burner