Application Guide - NP900 Series
20 (504
)
Table 3.1.1.5-16 Sequence current angle measurements in NP900.
Name
Range
Step
Description
Positive sequence
current angle
0.00…360.0deg
0.01deg Calculated positive sequence current
angle
Negative sequence
current angle
0.00…360.0deg
0.01deg Calculated negative sequence current
angle
Zero sequence current
angle
0.00…360.0deg
0.01deg Calculated zero sequence current angle
Table 3.1.1.5-17 Harmonic current measurements in NP900.
Name
Range
Step
Description
IL1 Harmonics
IL1 fund…IL1 31harm
0.00…1000000.0A
0.01A
Per unit, primary and secondary
harmonics per component for current
input IL1
IL2 Harmonics
IL2 fund…IL2 31harm
0.00…1000000.0A
0.01A
Per unit, primary and secondary
harmonics per component for current
input IL2
IL3 Harmonics
IL3 fund…IL3 31harm
0.00…1000000.0A
0.01A
Per unit, primary and secondary
harmonics per component for current
input IL3
I01 Harmonics
I01 fund…I01 31harm
0.00…1000000.0A
0.01A
Per unit, primary and secondary
harmonics per component for current
input I01
I02 Harmonics
I02 fund…I02 31harm
0.00…1000000.0A
0.01A
Per unit, primary and secondary
harmonics per component for current
input I02
3.1.2
V
OLTAGE MEASUREMENT AND SCALING
In NP900 series voltage measurement module (VT-module) is used for measuring the
voltages from voltage transformers and processing the measured voltages to
measurement database and for use of measurement- and protection functions (protection
function availability depends on IED type). For the measurements to be correct it is
essential to understand the concept of the NP900 series IEDs voltage measurements.
-
PRI
o
Primary voltage, the voltage
which flows in the primary circuit
and through primary side of the
voltage transformer.
-
SEC
o
Secondary voltage, the voltage
which the voltage transformer
transforms according to the ratio.
This voltage is measured by the
protection IED.
Figure 3.1.2-12 Voltage measurement terminology in NP900 platform
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...