Application Guide - NP900 Series
144 (504
)
A996A
Table 3.2.11.6-98. Event codes of the TOLF function instance
In the register of the TOLF function is recorded activated, blocked etc. “On” event process
data. In the table below is presented the structure of TOLF function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.11.6-99. Register content.
Date & Time
Event
code
Time to
reach 100%
theta
Ref. T
current
Active
meas
current
T at the
moment
Max
temp
rise
allowed
Temp
rise at
the
moment
Hot Spot
estimate
Hot
spot
max
all.
Trip
delay
rem
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
4288-
4297
Descr.
seconds
xIn
xIn
%
deg
deg
deg
deg
s
1 – 8
3.2.12
A
RC FAULT
ARCI>
(50ARC/50NARC)
Arc faults occur because of insulation failure, incorrect operation of the protected device,
corrosion, overvoltage, dirt, moisture, incorrect wiring or even because of aging caused by
electric load. To minimize the effects of the arc fault it’s important to detect the arc as fast
as possible. Using arc sensors to detect arc faults is much faster than merely measuring
currents and voltages. In busbar protection using just the normal protection IEDs could be
too slow to disconnect arcs under safe time. For example when setting up overcurrent
protection relay controlling the feeder breakers operation time could be necessary to delay
for hundreds of milliseconds after sensing the fault to achieve selectivity. This delay can
be avoided by using arc protection. To extent the speed of arc protection operation arc
protection card has high speed output as well to give tripping signal faster.
Arc protection card has four sensor channels. Up to three arc point sensors may be
connected to each channel. Sensor channels support ICEs NP-01 light and NP-02
pressure and light sensor units. Optionally protection function can be applied with phase
or residual current condition. This means that the function will trip only if light and current
Event
Number
Event
channel
Event block name
Event
Code
Description
4288
67 TOLF1
0 Alarm1 On
4289
67 TOLF1
1 Alarm1 Off
4290
67 TOLF1
2 Alarm2 On
4291
67 TOLF1
3 Alarm2 Off
4292
67 TOLF1
4 Inhibit On
4293
67 TOLF1
5 Inhibit Off
4294
67 TOLF1
6 Trip On
4295
67 TOLF1
7 Trip Off
4296
67 TOLF1
8 Block On
4297
67 TOLF1
9 Block Off
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...