Application Guide - NP900 Series
118 (504
)
A996A
Table 3.2.9.5-83. Event codes of the CBFP function instance
In the register of the CBFP function is recorded activated, blocked etc. “On” event process
data. In the table below is presented the structure of CBFP function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.9.5-84. Register content.
Date & Time
Event
code
Trigger
current
Time to
RETRact
Time to
CBFPact
Ftype
Stype
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
2817-
2818
Descr.
Phase
and
residual
currents
on
trigger
time
Time
remaining
before
RETR is
active
Time
remaining
before
CBFP is
active
Monitored
current
status
code
Activated
start
triggers
1 - 8
3.2.10
R
ESTRICTED EARTH FAULT
/
CABLE END DIFFERENTIAL
(REF)
I0
D
>
(87N)
Restricted Earth Fault function (REF) is used for residual differential current measurement
for transformers and also this function can be used for Cable End Differential (CED)
functionality. Operating principle is low impedance differential protection with settable bias
characteristics where differential current is calculated in between of summed phase
currents and selected residual current input. In CED mode the function provides natural
measurement unbalance compensation in order to have higher operating sensitivity for
monitoring cable end faults.
REF function constantly monitors phase currents and selected residual current instant
values as well as calculated bias current and differential current magnitudes of.
Blocking signal and setting group selection controls the operating characteristics of the
function during normal operation.
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
2817
44 CBF1
1 Start ON
1
2818
44 CBF1
2 Start OFF
0
2819
44 CBF1
3 Retrip ON
1
2820
44 CBF1
4 Retrip OFF
0
2821
44 CBF1
5 CBFP ON
1
2822
44 CBF1
6 CBFP OFF
0
2823
44 CBF1
7 Block ON
1
2824
44 CBF1
8 Block OFF
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...