Blade Series Heat Exchanger 

Operation and Installation 

 

*IMPORTANT* 

For safe and satisfactory operation, please read the following instructions.  Keep  

these instructions for future reference.  Some information may not apply to your system

.

 

 

Introduction 

Ice Qube

 Heat Exchangers are closed-loop systems that have been designed to provide cooling for computer and 

electronics enclosures in environments where the enclosure temperature may be maintained at temperatures at least 5 
degrees Fahrenheit above ambient.  Models range from 16.7 to 105.5 watts/degree Fahrenheit cooling capacity.   
 
The Blade Series heat exchangers offer unique features such as a built-in heating system, and the ability to operate with 
a VAC or VDC power supply.  Connecting both a VAC and a VDC power supply provides a redundant power supply system 
where if AC power is lost, the model will continue to operate on a DC power supply.     

 

Basic Operation 

Ice Qube 

Heat Exchangers have only two moving parts.  They are maintenance-free fans or blowers, which are used 

to move air over the heat exchanger core.  The enclosure fan moves hot air from the top of enclosure, through the heat 
exchanger core where the heat is dissipated and the cool air returns to the bottom of the enclosure.  The ambient fan 
moves cool air from near the bottom of the heat exchanger through the core where the heat from the enclosure is 
absorbed and dissipated to the ambient air near the top of the heat exchanger

 

 

Unpacking Inspection                   

Look for damage to the shipping container.

  

If the shipping container has been damaged or marred in any way, carefully 

inspect the heat exchanger for damage which may have occurred during shipping.  Check for scratches, dents, or any 
other irregularities.  Listen for noises that could indicate loose components.  Any evidence of damage should be recorded 
on the freight bill.  The freight carrier’s claim procedure should be followed.   

 

Ice Qube Inc. cannot accept responsibility

 

for damages which occur during shipping. 

 

Pre-installation Test 

Before installing the heat exchanger on the enclosure, it is recommended to operate the unit for a few minutes to be sure 
it is functioning properly.  Although the system has been factory tested, damage may have occurred during shipping 
which may have not been apparent during the unpacking inspection. 
 

1.

 

Place the system on a solid base such as a workbench or table.  Be sure there is adequate space for the two air 
streams. 

 

2.

 

Check the unit name plate for electrical requirements.  Note that power supply may be VAC or VDC.  Connect 
the power cord to the model and a properly grounded electrical outlet of sufficient capacity.  The use of an 
extension cord is not recommended.     
** 

If any unusual noise or vibration is present, immediately disconnect the power cord and inspect the unit for 

the cause.

 

 

3.

 

After power is supplied to the unit, the controller will begin an approximate 90 second self-diagnostic 
where it will check sensor, fan and heater operation.  Note: Heat does not function with 48 VDC power 
supply only and will alarm.  This alarm will auto reset at the end of the diagnostic sequence. 

 

4.

 

After making these few simple checks, you are ready to prepare your electrical enclosure for installation 
of the heat exchanger. 

 

 

 
 

 

Содержание Blade Series

Страница 1: ...g container If the shipping container has been damaged or marred in any way carefully inspect the heat exchanger for damage which may have occurred during shipping Check for scratches dents or any other irregularities Listen for noises that could indicate loose components Any evidence of damage should be recorded on the freight bill The freight carrier s claim procedure should be followed Ice Qube...

Страница 2: ... the original thickness to maintain enclosure integrity 6 Connect power to the unit from a properly grounded power supply of sufficient capacity The controller will then begin an approximate 90 second self diagnostic where it will check the sensor fan and heater operation Note Heat does not function with 48 VDC power supply only and will alarm This alarm will auto reset at the end of the diagnosti...

Страница 3: ... running and continue to operate until the temperature inside the equipment rises by 7 4 Press or to set the temperature you want The temperature adjustment range is 22 F to 68 F 30 C to 20 C NOTE Don t forget to review the high and low alarm temperature when the Fan start temperature and heating start temperature are changed 5 High Temperature Alarm Setting Default set to 131 F Press Select to co...

Страница 4: ... same with the speed regulation point temperature of inner fan 11 Outside Fan full speed temperature setting Default set to 108 F Press Select to enter the Outside Fan full speed temperature setting When are on press or to enter parameters settings LCD will show the full speed point temperature Setting range is 93 F to 140 F 34 to 60 The Outside Fan will reach High speed at this temperature settin...

Страница 5: ...elected for the alarm function the audible alarm will not function 17 Temperature Unit Setting Default set to F Press Select to enter the temperature unit setting When or is lit F or C will appear on the LCD screen accordingly Press or to change the setting 18 Controller Password Setting Default set to 1 2 3 4 Press Select Now PIN will show on the screen To set a new user PIN code press The displa...

Страница 6: ...8 15 REV1 6 WIRING SCHEMATIC 100HE CF ...

Страница 7: ...trical power available at the outlet YES NO Is the power cord connected to the electrical supply YES NO Is the controller set point temperature above or below the enclosure temperature YES NO Is the internal blower s operating YES NO Is the external blower s operating YES NO Is the enclosure door closed tightly YES NO Are all of the gaskets in place YES NO Has the unit been cleaned recently YES NO...

Страница 8: ...MS AND IS IN LIEU OF ALL OTHER WARRANTIES GUARANTEES EXPRESS OR IMPLIED ARISING BY OPERATION OF LAW COURSE OF DEALING CUSTOM USAGE OF TRADE OR OTHERWISE SPECIFICALLY EXCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE 1 The warranty and remedies for breach of warranty provided for in this Standard Warranty extend only to the original installation and do n...

Страница 9: ...ll Ice Qube support service at 724 837 7600 and work with the Ice Qube support personnel so that Ice Qube can determine the necessity of in field service for such Product in its sole discretion Ice Qube will not assume any liability for any in field service not initiated by Ice Qube In no event shall Ice Qube be liable for any incidental special indirect consequential or similar damages incurred b...

Отзывы: