21
VI. Electrical wiring diagram
1. Notice
•
The power supply voltage must conform to the rated voltage
.
•
Wiring must be carried out by a professional and wired in accordance with wiring diagram
.
•
Ensure the power supply wires are properly sized and protected from excessive current (please refer
to the performance specification and parameters table for details)
.
•
Units shall be grounded and wired per national wiring electrical code.
•
The power and ground wires must be tightened by applying the right torque with the right tools.
•
Only the electrical components specified by the company can be used, and the installation and
technical services are required from the designated manufacturer or authorized dealer. If the wiring is
not in accordance with the electrical installation specifications, it may lead to the failure of the controller
or electric shock
.
•
According to the national technical standards for electrical equipment, set up leakage protection
devices
.
•
After all the wiring is completed, the power can be connected only after careful inspection
.
•
Please read the labels on the electrical cabinet
.
•
The power supply wire for outdoor installation of the unit shall not be lower gauge than the neoprene
armored flexible cord (line 57 in IEC 60245), and the wire diameter specification of the power supply
wire shall be selected according to the rated maximum current of the nameplate, as shown in the table
below
:
Maximum current (A)
Area of wire (
mm²) Switch nominal specification( A)
≤16
≥2.5
25 A
≤25
≥4
32 A
≤32
≥6
40 A
≤41
≥6
50A
≤57
≥10
63 A
≤76
≥16
80 A
≤101
≥25
100 A
≤125
≥35
125 A
≤135
≥50
160A
•
When the power supply is connected, it must be equipped with a full-pole disconnection device
matching with the unit and at least 0.12 inches contact distance from the power supply and a leakage
protection device
.
•
If the supply cord is damaged, it must be replaced by a professional in the designated manufacturer's
maintenance department or similar department to avoid danger
.
•
The power supply shall be housed in a weather tight enclosure, 60 inches or more above the ground. It
is forbidden to be installed in a moist, acidic, corrosive environment or exposed to direct sunlight
.
Содержание ccHPWH Series
Страница 11: ...8 III Product specification 1 Dimensions Unit inch ccHPWH275 S ccHPWH275 D ...
Страница 12: ...9 ccHPWH550 S ccHPWH550 D ...
Страница 26: ...23 2 Wiring diagram ccHPWH275 S ccHPWH275 D ...
Страница 27: ...24 ccHPWH550 S ccHPWH550 D ...
Страница 42: ...39 Schematic diagram of control wiring and code dialing of each module ...