37
ICC
8.7.2
BACnet /IP Client
To configure the BACnet/IP client, click on the
Ethernet Configuration
tab,
check
BACnet/IP Client
in the protocol dropdown menu to enable the driver, and
then click on the
BACnet/IP Client
subtab. The gateway can read and write the
present value property of BACnet objects hosted by other devices on the
network. This behavior is defined by configuring BACnet service objects. For
more information on service objects, refer to section 8.5. Whenever the
BACnet/IP client driver is enabled, the BACnet device object is always present
and must be properly configured. If the BACnet/IP server is enabled, the device
object configuration from the client will have priority. This section will discuss
how to configure the BACnet/IP client.
Scan Rate
This is the time in milliseconds the device will wait between sending requests.
This may be useful if BACnet devices that the gateway is communicating with
require additional time between requests, or to reduce overall network utilization.
If no additional time is required, set this field to 0.
8.7.2.1
Device Object Configuration Group
The Device Object Configuration group contains several fields that must be
appropriately set for each device residing on a BACnet network.
Device Name
This field is the BACnet Device Object’s name. The device name must be unique
across the entire BACnet network. Enter a string of between 1 and 32 characters
in length.
Instance Number
This field is the BACnet Device Object’s instance number. The instance number
must be unique across the entire BACnet network. Enter a value between 0 and
4194302 (0x0 – 0x3FFFFE).
8.7.2.2
BACnet Service Object Configuration
The following describes the configurable fields for a BACnet service object. For
more information on BACnet service object editing options, refer to section 8.6.
Up to 100 service objects can be created.
Type
The radio buttons in this group select the BACnet object type. Choose from
Analog Input, Analog Output, Analog Value, Binary Input, Binary Output, or
Binary Value.
Содержание ETH-1000
Страница 44: ...43 ICC 8 7 4 BBMD Currently the BBMD is only configurable via the embedded web page Refer to section 10 11...
Страница 60: ...59 ICC Figure 10 MELSEC Client Concept...
Страница 158: ...157 ICC Figure 22 Core FTP in Connected State...
Страница 208: ...207 ICC SMin SMax Min Max multiplier Equation 1 SMin offset Equation 2...