Procedure
To ensure that the installation site meets the requirements, complete the following
steps:
1.
Use adequate ventilation, especially during the first 120 days of continuous
operation. Ensure that there is an average room outdoor intake air rate of 0.4
air change per hour.
2.
Keep front and rear of the rack clear of obstruction.
3.
Verify that you can meet the environmental operating requirements at the air
intake locations.
4.
Consider optimizing the air circulation and cooling for the rack by using a
raised floor, adjusting the floor layout, and adding perforated tiles around the
air intake areas.
Operating environment requirements
You must verify that your operating environment is compatible with the required
specifications.
With or without the rear-door heat exchanger option, the air that enters the front
door of the XIV system must meet the following requirements.
Operating (powered on)
v
Temperature: 10 - 35°C (50 - 95°F)
v
Relative humidity: 20 - 80%, non-condensing
v
Maximum wet bulb temperature: 25°C (77°F)
v
Maximum altitude: 2134 m (7000 ft)
Non-operating (powered off)
v
Temperature: 5 - 45°C (41 - 113°F)
v
Relative humidity: 20 - 80%, non-condensing
v
Maximum wet bulb temperature: 27°C (80.6°F)
Shipping
v
Temperature: -40 - 60°C (-40 - 140°F)
v
Relative humidity: 5 - 95%, non-condensing
v
Maximum wet bulb temperature: 29°C (84.2°F)
Important:
An XIV system that runs continuously must be within the specified
operating environment. An XIV system can operate at the maximum allowable
temperature for only short durations, such as might occur during a disk drive
module or power-supply unit replacement. Continuous operation above the
maximum temperature increases the probability of component failure.
Air enters at the front of the rack and leaves at the back. To prevent the air that is
leaving the rack from entering the intake of another piece of equipment, place
racks in alternate rows, in a back-to-back, and front-to-front arrangement. Align the
front of racks on a floor-tile seam, with a full line of perforated tiles immediately
in front of the rack, and with the air temperature at the front of the rack less than
27ºC (80.6ºF).
System environmental acclimation
Condensation is a normal and natural occurrence if packaging is removed at time
of delivery, during extreme cold weather delivery times.
42
IBM XIV Gen3 281x-11x, 281x-21x, and 281x-314 Planning Guide
Содержание XIV Gen3 Series
Страница 1: ...IBM XIV Storage System Gen3 Models 281x 11x 281x 21x and 281x 314 Planning Guide SC27 5412 09 IBM...
Страница 6: ...vi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 8: ...viii IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 10: ...x IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 16: ...xvi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 24: ...xxiv IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 52: ...28 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 87: ...AIX 7 Oracle Solaris 11 SPARC Solaris 11 INTEL HPUX HPUX 11i v3 IA64 Chapter 8 Management tool requirements 63...
Страница 88: ...64 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 94: ...70 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 116: ...92 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 125: ......
Страница 126: ...IBM Printed in USA SC27 5412 09...