Figure 39. Side fan assembly replacement
4. Close and latch the cabinet rear door, if applicable.
TMF/TFD replacement procedure
Use the following procedure to replace the TMF/TFD module in a SAN256N director.
Removing the TMF/TFD module
1. Shut down the SAN256N director. Refer to “Powering off the SAN256N director” on
2. Remove the three upper fan assemblies to allow access to the TMF/TFD module.
Refer to “Upper fan assembly replacement procedure” on page 87.
3. If external top cabinet fans are installed in the SANC40N cabinet, disconnect the
cables from the TMF/TFD module DB9F connectors.
Side fan assembly
1. Slide latch to LEFT
2. Push housing forward
to unlatch, release
to Mount into Chassis
to lock
Side fan I/O connector
To Midplane side
fan connector
Attention: Refer to safety notices before starting an installation.
Attention: This procedure requires that all Upper Fan assemblies (and if installed,
external cabinet fans ) are removed from the SAN256N director chassis. The SAN256N
system must be shut down during the TMF/TFD module replacement to prevent the
internal SAN256N modules (TFIO, TCM, and TSW) from being subjected to higher than
recommended operating temperatures.
Attention: Use a properly attached ESD wrist strap when handling the TMF/TFD
module, otherwise damage to equipment may result.
Содержание TotalStorage SAN256N Director 2045-N16
Страница 2: ......
Страница 3: ...IBM TotalStorage SAN256N Director 2045 N16 Installation and Maintenance Guide GC26 7714 00...
Страница 10: ...SAN256N Director 2045 N16 viii...
Страница 12: ...SAN256N Director 2045 N16 x...
Страница 18: ...SAN256N Director 2045 N16 xvi...
Страница 26: ...SAN256N Director 2045 N16 6...
Страница 84: ...SAN256N Director 2045 N16 64...
Страница 94: ...SAN256N Director 2045 N16 74...
Страница 97: ...Chapter 5 Hardware maintenance procedures 77 Figure 33 SAN256N director front chassis FRU locations 1 2...
Страница 120: ...SAN256N Director 2045 N16 100...
Страница 142: ...SAN256N Director 2045 N16 122...
Страница 144: ...SAN256N Director 2045 N16 124...
Страница 156: ......
Страница 157: ...Printed in USA GC26 7714 00...