Ensure that the airflow and cooling are adequate and there is sufficient clearance
around the air vents on the switch, as described in Appendix A, “Product
Specifications,” on page 99.
The rack must have sufficient vertical clearance for the chassis along with 2 RU for
the shelf brackets, and any desired clearance for the installation process.
The front and rear doors of enclosed racks must have at least 60% open area
perforation pattern.
Additionally, you must consider the following site requirements for the rack:
v
Power receptacles must be located within reach of the power cords used with
the switch.
v
AC power supplies
v
Power cords for 3-kW AC power supplies are 8 to 12 feet (2.5 to 4.3 m) long.
v
DC power supplies
v
Power cords for 3.0-kW DC power supplies are supplied and dimensioned by
the customer.
v
HVAC/HVDC power supplies
v
Power cords for 3.5-kW HVAC/HVDC power supplies are 14 feet (4.26 m) long.
v
Where necessary, have a seismic rating of Network Equipment Building
Standards (NEBS) Zone 3 or Zone 4, per GR-63-CORE.
Rack and Cabinet Requirements for the SAN768C-6 Chassis
To correctly install the switch in a cabinet located in a hot-aisle/cold-aisle
environment, you should fit the cabinet with baffles to prevent exhaust air from
recirculating into the chassis air intake. Work with your cabinet vendors to
determine which of their cabinets meet the following requirements or see the IBM
Support for recommendations:
v
The height of the rack or cabinet must accommodate the 25 RU (43.75 inches or
111.1 cm) height of the switch and its bottom support bracket.
v
Minimum gross load rating of 2000 lb (907.2 kg) (static load rating) if supporting
two switches.
Rack and Cabinet Requirements for the SAN384C-6 Chassis
The rack must meet the following requirements:
v
The minimum vertical rack space per chassis is 24.5 inches (62.2 cm) or 14 RU.
v
The width between the mounting rails must be at least 17.75 inches (45.1 cm).
For four-post EIA racks, this is the distance between the two front rails and rear
rails.
To correctly install the switch in a cabinet located in a hot-aisle/cold-aisle
environment, you should fit the cabinet with baffles to prevent exhaust air from
recirculating into the chassis air intake. Work with your cabinet vendors to
determine which of their cabinets meet the following requirements or see the IBM
Support for recommendations:
v
The height of the rack or cabinet must accommodate the 14-RU (24.5 inches or
62.2 cm) height of the switch and its bottom support bracket.
v
Minimum gross load rating of 2000 lb (907.2 kg) (static load rating) if supporting
three switches.
42
SAN192C-6, SAN384C-6 and SAN768C-6 Installation, Service, and User Guide
Содержание SAN192C-6
Страница 2: ......
Страница 8: ...vi SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 10: ...viii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 24: ...xxii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 114: ...90 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 122: ...98 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 142: ...Figure 44 AJK5 Figure 45 AJJX Figure 46 AJK4 118 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 143: ...Figure 47 AJK2 Figure 48 AJK1 Figure 49 AJJY Appendix B Cable and Port Specifications 119 ...
Страница 144: ...Figure 50 AJJV 120 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 146: ...122 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 158: ...134 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 159: ......
Страница 160: ...IBM Part Number 02JD693 Printed in USA SC27 9276 00 1P P N 02JD693 ...