Power and cabling information for NEBS (Network
Equipment-Building System) GR-1089-CORE
The equipment is suitable for installation in the following:
v
Network telecommunications facilities
v
Locations where the NEC (National Electrical Code) applies
The intrabuilding ports of this equipment are suitable for connection to
intrabuilding or unexposed wiring or cabling only. The intrabuilding ports of this
equipment
must not
be metallically connected to the interfaces that connect to the
OSP (outside plant) or its wiring. These interfaces are designed for use as
intrabuilding interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE) and require isolation from the exposed OSP cabling. The addition
of primary protectors is not sufficient protection to connect these interfaces
metallically to OSP wiring.
Note:
All Ethernet cables must be shielded and grounded at both ends.
The ac-powered system does not require the use of an external surge protection
device (SPD).
The dc-powered system employs an isolated DC return (DC-I) design. The DC
battery return terminal
shall not
be connected to the chassis or frame ground.
Product recycling and disposal
Ensure that you are aware of the materials that must be recycled. Before using this
information and the product that it supports, read the
IBM Environmental Notices
and User Guide
on the SAN Volume Controller Documentation CD.
xii
IBM System Storage SAN Volume Controller: Models 2145-8F2 and 2145-8F4 Hardware Installation Guide
1
1
1
Содержание SAN Volume Controller 2145-8F2
Страница 2: ......
Страница 8: ...vi IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 24: ...xxii IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 54: ...30 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 78: ...54 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 80: ...56 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 88: ...64 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 95: ......
Страница 96: ...Printed in USA GC27 2221 00...