Battery charge values without loads
The fully-charged, no-load connected battery voltages for the UPS models are
described in the following table.
Table 13. Battery voltages
UPS
Type-
model
Battery VDC
Nominal
Minimum
IBM 6000 VA UPS
(200 V / 208 V)
5395-6AX
108
113.4
IBM 6000 VA UPS (230 V)
5395-6KX
108
113.4
The voltage values are indicated for one battery only. To measure the voltage value,
you must disconnect any batteries that are connected to each other. The battery
voltage must be measured at the battery connectors as shown in the following
illustration.
OK
OK
100%
6
m
in
1500
VA
208
V
/60hz
UPS ON
Positive
(red)
Ground
(black)
For more information about battery charge values without loads, see the Retain tip:
H202830 at http://ibm.com/support/entry/portal/docdisplay?lndocid=migr-5087624.
44
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Содержание 6000 VA LCD 4U
Страница 1: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 87: ......
Страница 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...