a.
In the navigation area, click the Resources icon
, and then click All Systems.
b.
Click the system name for which you want to deactivate partitions.
c.
Select the logical partitions that you want to deactivate.
d.
In the content pane, click Actions > Deactivate.
e.
Click OK.
2.
To power off the system, complete the following steps:
a.
In the navigation area, click the Resources icon
, and then click All Systems.
b.
Select the system that you want to power off.
c.
In the content pane, click Actions > View All Actions > Power Off.
d.
Click OK.
Stopping an IBM PowerKVM system
You can use the Intelligent Platform Management Interface (IPMI) to stop an IBM PowerKVM system.
To stop an IBM PowerKVM system, complete the following steps:
1.
Log in to the host as a root user or with sudo authority.
2.
To power off each of the guests, complete the following steps.
a.
To obtain a list of all guests, type
virsh list
.
b.
For each guest in the list, type
virsh shutdown
domain name or type
virsh shutdown
domain ID.
Note:
Type
virsh list
to verify whether all the guests are powered off. If any guest is not powered off,
type
virsh destroy
domain name or type
virsh destroy
domain ID to power off the guest.
3.
Run the
ipmitool -I lanplus -H
FSP IP
-P
ipmipassword
chassis power off
command from a remote
system.
Starting the system or logical partition
Learn how to start a system or logical partition after performing a service action or system upgrade.
Starting a system that is not managed by an HMC
You can use the power button or the Advanced System Management Interface (ASMI) to start a system
that is not managed by a Hardware Management Console (HMC).
Starting a system by using the control panel
You can use the power button on the control panel to start a system that is not managed by a Hardware
Management Console (HMC).
To start a system by using the control panel, complete the following steps:
1.
Open the front rack door, if necessary.
2.
Before you press the power button on the control panel, ensure that power is connected to the system
unit as follows:
v
All system power cables are connected to a power source.
v
The power LED, as shown in the following figure, is slowly flashing.
v
The top of the display, as shown in the following figure, shows
01 V=F
.
Reference information
27
Содержание 5147-024
Страница 1: ...Power Systems Installing the Model 024 ESLL or ESLS storage enclosure GI11 9921 01 IBM...
Страница 2: ......
Страница 3: ...Power Systems Installing the Model 024 ESLL or ESLS storage enclosure GI11 9921 01 IBM...
Страница 6: ...iv Power Systems Installing the Model 024 ESLL or ESLS storage enclosure...
Страница 16: ...xiv Power Systems Installing the Model 024 ESLL or ESLS storage enclosure...
Страница 62: ...46 Power Systems Installing the Model 024 ESLL or ESLS storage enclosure...
Страница 63: ......
Страница 64: ...IBM Part Number 01LK529 Printed in USA GI11 9921 01 1P P N 01LK529...