manualshive.com logo in svg
background image

Содержание 4300

Страница 1: ... __y Systems GA24 3667 1 File No 4300 15 IBM 4300 Processors Installation Manual Physical Planning ...

Страница 2: ...onal Characteristics and Proc essor Complex Configurator GA33 1526 IBM 4331 Physical Planning Template GX24 3728 IBM 4341 Functional Characteristics and Proc essor Complex Configurator GA24 3672 IBM 4341 Physical Planning Template GX24 3729 Assembly of Coaxial Cable and Accessories and Attachment to IBM Products GA27 2805 IBM 3270 Information Display Station Installa tion Manual Physical Planning ...

Страница 3: ...Safety and Fire Precautions 1 11 1 6 1 Emergency Lighting 1 11 1 6 2 Computer Location 1 12 1 6 3 Fire Prevention Considerations 1 12 1 6 4 Computer Area Fire Prevention Equipment 1 12 1 6 5 Data Storage 1 12 1 6 6 Supporting Facilities 1 12 1 6 7 Preplanning to Continue Operation in An Emergency 1 13 1 6 8 General Precautions and Personnel Training 1 13 1 6 9 Additional Reference Material l 13 1 ...

Страница 4: ......

Страница 5: ...area For details see section 1 2 1 Space and LayoutRequire i ments 4 Advise IBM of any special security procedures physical access restrictions or other require ments 5 Study availability and delivery quotations for power air conditioning cables not supplied by IBM and other equipment to determine when each item must be ordered and delivered Six Months before equipment delivery 1 Verify the air co...

Страница 6: ...ea required for the equipment is de termined by the specific components to be in stalled the location of columns provision for future expansion floor loading capacity etc 2 As a preliminary check for clearance problems paper templates of the units made to the scale of your building plans can be used on the building plan itself It may be convenient to make a rigid full scale template of the largest...

Страница 7: ...n planning the lay out 1 Flow of work and personnel within the area 2 Operator access to units as required 3 If the equipment is not to be installed on a raised floor consider a The maximum cable lengths b The need for mechanical protection such as cable guards or ramps for the safety of per sonnel and equipment 4 The effect of channel sequence or priority on the physical layout of the units 5 The...

Страница 8: ...ee Access Floor Subframing Supported Panels Panels Removable Cutouts in Panels Note A raised floor panel lifter should be made readily available in the computer room at a convenient location Figure l 1 Types of Raised Floors 14 IBM 4300 Proc 11sors Installation Manual Physical Planning 4 Permits the space between the original floor and the raised floor to bc 1 used to supply air to the equipment a...

Страница 9: ...al shock 2 Maintaining the room humidity within control limits as defined in section 1 3 2 Temperature and Humidity Design Criteria 1 2 4 Furniture Furniture can provide a source of high static charge Ensure that seat covers etc are made of materials that resist static buildup Many plastics permit the buildup of high static charges Cloth covered chairs are normally less susceptible to generating s...

Страница 10: ...sonnel heat dissipation Latent load Lighting Fresh air introduction Possible reheat Heat conduction through outer walls Ceiling Floors Door openings Partitions Glass wall area Computer room cooling is basically a sensible as opposed to a latent cooling operation Sensible heat is defined as the transfer of thermal energy to or from a substance resulting in a change in tempera ture Latent heat is th...

Страница 11: ...midity Design Criteria The data processing equipment can tolerate a con siderable range of temperature and humidity as de scribed on the Specifications pages for each unit An air conditioning system should be designed to maintain 24 C 75 F and 50 percent relative hu midity at altitudes up to 2 150 meters 7 000 feet This design criteria provides for the largest buffer in terms of available computer...

Страница 12: ...ions 1 8 IBM 4300 Proces sors Installation Manual Physical Planning 1 3 4 1 Mechanical Air Filters Mechanical air filters must be rated at a minimum of 20 percent efficiency This rating applies to a clean filte and must be maintain d throughout the life of the filter 1 3 4 2 Electrostatic Plate Filter Electrostatic plate filters must be rated at a minimum of 85 to 90 percent efficiency Electrostat...

Страница 13: ...able IBM I 0 equipment 1 4 2 Frequency Limits The line frequency must be maintained at 60 or 50 1 2 Hz depending upon the rating of the equip ment 1 4 3 Line to Line Voltage Imbalance In a three phase system any three line to line equip ment voltages must not differ by more than 2 5 per cent from the average of the three voltages All three line to line voltages must be within the limits specified ...

Страница 14: ...g Terminal Bar Feeders 5 Wire Metallic Cold Water Pipe Building Steel or Driven Ground Rod 1 10 IBM 4300 Processors Installation Manual Physical Planning i _ Circuit Breakers of Appropriate Size Branch Circuits Customer Supplied Receptacles Connectors in Accordance with Local Codes Legend Phase Wires and Neutral Insulated Green Wire Ground Install isolation or step down transformer if required For...

Страница 15: ...alled in the con puter room and the CE area for use by building ma ntenance personnel service rep resentatives etc cfonvenience outlets should be on the lighting or oth r building circuits not on the computer power p nel or feeder For detailed re quirements see seqtion 1 10 Customer Engineering Support Facilities I Under no circum tances are the service outlets on IBM units to be us d for any purp...

Страница 16: ...d for use on the electrical equipment 3 Portable pressurized water extinguishers should be provided for ordinary combustible material such as paper 1 12 IBM 4300 Processors Installation Manual Physical Planning 4 Extinguishers should be readily accessible to indi viduals in the area Extinguisher locations should be visibly marked overhead 5 Where portable cylinders are used as the primary extingui...

Страница 17: ... a Method and sequence of shutting off all elec trical power b Shutting off air conditioning systems c Calling fire company d Handling fire extinguishers and small diameter fire hoses e Evacuating records f Evacuating personnel g Administering first aid 1 6 9 Additional Reference Material Consult NFPA Standard No 75 Protection of Elec tronic Computer Data Processing Equipment or applicable local o...

Страница 18: ...valent tothe exposure It is not necessary to condition this me di um for more than 24 hours Your storage facilities should be fire resistant en closures located away from magnetic fields Magnet ic fields of greater than 24A cm 30 oersteds can cause loss of data or introduction of noise Additional information concerning handling oper ation device dimensions flammability characteris tics shipping re...

Страница 19: ...provide a scaled layout to assist in locat ing the equipment receptacles lights and so forth in the service area This area should contain a conven ience outlet which should not be powered from the computer power panel The IBM Physical Planning Template Field Engi neering Furniture and Test Equipment GX22 6925 is available to assist in planning this space 1 11 Remote Support Facility The optional R...

Страница 20: ...herwise noted on the specifi cation page The length is measured from the symbolffi 2 Unless otherwise noted locating dimensions are measured from edge of frame not cover Figure 1 3 Standard Symbols 1 15 Abbreviations and Definitions A ac A cm ampere alternating current amperes per centimeter 1 16 IBM 4300 Processors Installation Manual Physical Planning 1 14 Symbols used in Plan Views Figure 1 3 s...

Страница 21: ...direct access storage facility nom nominal DAU data adapter unit NTT Nippon Telephone and Telegraph de direct current dist distribution OD outside diameter dply display OEM original equipment manufacturer DRC data recording control oersted centimeter gram second electromagnetic unit of EBCD extended binary coded decimal magnetizing force A cm 1 256 oersteds EBCDIC extended binary coded decimal int...

Страница 22: ...l Newsletter VFL variable field length UK United Kingdom w watt UL Underwriters Laboratory WE Western Electric U S A United States of America WT IBM World Trade I I 1 18 IBM 4300 Processors Installation Manual Physical Planning ...

Страница 23: ...ric Scale 10 mm 0 5 m Dimensions English measurements are shown in parentheses Front Side Height mm 1 590 815 735 I 1590 inches 62 3 4 32 29 62 3 4 0 01 Service Clearances 815 Front 32 o mm 900 0 inches 35 1 2 I 900 Weight I 35 1 2 kg 57 _Jl lb 125 L u Processor Specifications and Cabling Schematics 4300 1 ...

Страница 24: ... I 4300 2 Installation Manual Physical Planning ...

Страница 25: ...I 16 3181 l_ 111811 I I 11 71 I 360 II 114 3 8 Front 1 295 I 1 __ Ji f 1ci 2 _3 j Notes 3175 1125 1 A console table is available from IBM as an optional feature 2 Cable entry exit holes are measured from edge of frame not covers Cable Entry Floor Cutout Dimensions Exit Number Millimeters Inches 1 200 x 330 8 x 13 2 100 x 250 4 x 10 3 180 x 200 7x8 4 100 x 150 4x6 Processor Specifications and Cabli...

Страница 26: ... Receptacle Connector R S 3743 Provided by Customer R S 3912 Provided by Customer 4331 2 Installation Manual Physical Planning World Trade Countries Except Canada The machine is shipped without plug This is customer provided according to local codes and national requirements Power Cord Style A6 See Appendix A in IBM1nput Output Equipment Installation Manual Physical Planning for System 360 System ...

Страница 27: ...r Cables Maximum of Eight 4023 ___ 3278 2A Control 5425 MFCU de common ground 4046 Remote Support Facility 5424 Multi Function Card Unit Signal Cables 8809 Magnetic Tape Unit External Signal Cable IBM Devices 4046 External Signal Cable Non IBM Devices A 10 m 33 ft fixed length interface cable 7 6 m 25 ft usabl l length is shipped with the proC8 Sor One 3278 2A Console Display Fixed cable length 7 ...

Страница 28: ...cessor CA U S A Japan nonswitched line with integrated 4 prong 10 33 l modem plug 4021 2831 1 Processor CA WT switched line with integrated modem 4 spade I0 33 3 8 lugs 4023 2832 1 Processor CA WT nonswitched line with integrated modem 4 spade 10 33 4 lugs 4039 3701 2 Processor CA U K Post Office Modem 25 pin with male 2835 4040 1020 2 Processor CA U K Autocall Unit 16 pin 10 33 with male 2835 404...

Страница 29: ...ont 13 1 4 25 1 1590 1s2 3t4l J 290 11 7 16 750 2X 29 1 2 _1 11001 43 1 4l I 3 5 j _ _ck I _lj 137 3 4 Cable Entry Dimensions Exit Number Millimeters Inches 1 110x665 4 x 26 2 40 x 270 1 Ya x 10 Ya 3 100 x 130 4 X5 4 100 x 130 4x5 _ 5 85x55 3 Ya x 2 Noi8 1 Ac onsole Jble is available from IBM as an optional feature 2 Cpf le entry exit holes are measured from edge of frame not covers Processor Spec...

Страница 30: ...901 l m 58 7 1 I iii 21 1 1 61 62t 3 41 12a 1181 I 4 3 oil8 o I I 1s5 6 1 9l 750 2X I 414 129 1121 1 100 I 16 1 41 _J_ 43 1 4 Front I _ _ _ 2 41_ _ _ I _ tj 3 500 137 3 4 _ _ _ _ _ _ _ _ 4341 2 Installation Manual Physical Planning Cable Entry Dimensions Exit Number Millimeters Inches 1 110 x 665 4x 26 2 40 x 270 1 x 10 3 100 x 130 4x5 4 100x130 4x5 5 85x 55 3 x 2 6 155 x 280 6 x 11 Note 1 A conso...

Страница 31: ... Frame 01 Frame 02 Front Rear Right 1100 1110 1105 43 1 4 43 3 4 43 1 2 515 kg 1140 lb 305 kg 670 lb Left 1 580 62 1 4 Left 1 580 62 1 4 Frame 03 185 kg 400 lb Channel to Channel Feature Total 1005 kg 2210 lb Heat Output 4 050 W 13 800 BTU hr maximum 4 400 W 15 000 BTU hr with Channel to Channel Feature Airflow m3 min cfm 37 downdraft 1300 Minimum shipping dimensions without covers Shipping withou...

Страница 32: ...t optionally 1 8 m 6 ft R S FS 3760 Provided by IBM R S FS 3754 Provided by Customer R S FS 3934 Provided by Customer World Trade Countries Except Canada The machine is shipped without plug This is customer provided according to local codes and national requirements Power Cord Style is DI See Appendix A in IBM Input Output Equipment Installation Manual Physical Planning for System 360 System 370 a...

Страница 33: ...ble length 7 6 m 25 ft between station and processor Ordered and shipped separately from 3278 2A Any combination of three units maximum 3287 Printers and or 3278 2A Display stations Maximum length 1 500 m 4921 ft Standard Power Interface Sequence and Control Cable Maximum Entry Length Notes 4 30 5 m 100 ft 1 2 4045 1 Processor External Signal 4 66 m 217 ft for non IBM equipment Notes 1 Available a...

Страница 34: ... 4341 6 Installation Manual Physical Planning ...

Страница 35: ...0 inches 34 29 55 Service Clearances Front Rear Right Left mm 760 760 460 0 inches 30 30 18 0 Weight kg 260 Ob 570 Heat Output Watts 880 Btu hr 3000 Airflow Convection Power Requirements kVA 1 3 Phases 1 Voltages SO Hz 200 220 235 60 Hz 200 208 230 not available in U S A Plug R S FS3120 Provided by IBM Receptacle R S FS3743 Provided by Customer Connector R S FS3913 Provided by Customer Power Cord ...

Страница 36: ... 5424 2 IBM 4300 Processors Installation Manual Physical Planning ...

Страница 37: ... GX24 3729 Metric and English Units 5424 GX21 9294 Metric Units 5424 GX21 9386 English Units For channel attached I O equipment template order numbers refer to IBM Input Output Equipment In stallation Manual Physical Planning for System 360 System 370 and 4300 Processors GC22 7064 Template List C 1 ...

Страница 38: ... C 2 IBM 4300 Processors Installation Manual Physical Planning ...

Страница 39: ... to be used In planning space requirements have you considered a Future expansion b Floor loading c Fire protection d Safety of personnel and records e Security f Acoustics g Vibration h Potential for electromagnetic interference i Possibility of atmospheric contamination j Adequate access route for movement of equipment from receiving area to computer room ramps doors corridors elevators etc k Ri...

Страница 40: ...room 1 2 5 9 Determine lighting requirements 1 2 7 a General lighting adequate b Emergency lighting provided I 0 Determine air conditioning requirements 1 3 a Size the air conditioning load by summing requirements for all heat loads including personnel b Present facilities adequate c Humidity control required d Temperature and humidity recording devices provided e Air conditioning controlled by co...

Страница 41: ... backup power system planned Type 12 If previous equipment must be retained and operated while new units are being installed a Additional power required b Temporary power circuits required c Additional temporary air conditioning required d Temporary layout planned for the transition period e External cables available 13 Determine safety requirements 1 6 a Computer in a fire resistant area or room ...

Страница 42: ...ayout plan to IBM so that IBM supplied cables can be ordered 4 Verify plans for installing cables through permanent walls or floors 5 Confirm all contractor and vendor schedules to ensure that schedules are compatible with equipment delivery 6 Confirm that all telephone or PTT line installation schedules for Remote Support Facility and telecommunication equipment are compatible with equipment deli...

Страница 43: ...d immediately after equipment installation 4 Power facilities installed S Branch circuits tested for proper phase rotation 6 Physical facilities plastering painting decorating lighting ramps floors etc completed 7 Communication facilities voice and data lines data sets etc installed and tested 8 Remote Support Facility line and telephone handset installed and tested 9 Cable holes cut in floor pane...

Страница 44: ...JJ G 6 IBM 4300 Processors Installation Manual Physical Planning ...

Страница 45: ... electrostatic plate filter 1 8 emergency lighting 1 11 emergency room power off controls 1 11 environmental and shipping specifications 1 15 equipment layout 1 2 external cables 1 1 final layout 1 1 fire and safety precautions 1 11 fire prevention considerations 1 12 fire prevention equipment 1 12 floor construction 1 3 floor covering recommendations 1 5 floor layout design 1 1 floor loading 1 1 ...

Страница 46: ...ications 1 15 site preparation 1 1 space requirements 1 2 standard shipping and environmental specifications 1 15 storage of data recording media 1 13 support facilities customer engineer 1 15 supporting facilities 1 12 X 2 IBM 4300 Processors Installation Manual Physical Planning symbols used in plan views 1 16 temperature and humidity design criteria 1 7 temperature and humidity recording instru...

Страница 47: ... _J u u ...

Страница 48: ...sing Division 1133 Westchester Avenue White Plains N Y 10604 IBM World Trade Americas Far East Corporation Town of Mount Pleasant Route 9 North Tarrytown Y U S A 10591 IBM World Trade Europe Middle East Africa Corporation 360 Hamilton Avenue White Plains N Y U S A 10601 n I ...

Страница 49: ...lease direct any requests for copies of publications or for assistance in using your IBM system to your IBM representative or to the IBM branch office serving your locality Are you able to find information in this publication easily Are the illustrations adequate clear and concise Which of the following are included in your occupational responsibilities System operating Programming Maintaining If ...

Страница 50: ... print NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES Fold Your Name Company Name Department ______ Street Address Qty ___ State Zip Code IBM Branch Office serving you _ __ ___ _ International Business Machines Corporation Data PrOC811ing Division 1133 Westchester Avenue White Plains N Y 10604 IBM World Trade Americas Far East Corporation Town of Mount Pl88Mnt Route 9 North Tarrytown N Y U S ...

Отзывы: