8.2.3 Low Water Cut-off error
Low Water Cutoff Error
Issue
Diagnosis
Fix
Error - Low Water Cutoff
The Safety and Ignition
module has detected a low
water condition.
Refer to the
V10 Touchscreen
Controller
manual for
information on resetting a
boiler after a LWCO lockout.
8.2.4 Aux. Interlock 1 or 2
Aux. Interlock 1 or 2
Issue
Diagnosis
Fix
Interlock 1 or 2 terminals are
open.
Jumper lead is loose or
compromised.
Replace the jumper lead.
External safety is in an alarm
state.
Inspect the external safety
devices.
8.3 Miscellaneous touchscreen controller errors
Miscellaneous errors
Issue
Diagnosis
Fix
“ Loop/Indoor Sensor”
“Insufficient Air Flow”
“Insufficient Water Pressure”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back
of the controller board.
“Unknown Error”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back
of the controller board.
Temperature
sensor input
problem.
Test each temperature
sensor for appropriate
readings and Replace
defective temperature
sensor.
98
Section: Troubleshooting
Содержание SL Series
Страница 8: ...Intentionally left empty...
Страница 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Страница 14: ...Intentionally left empty...
Страница 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Страница 76: ...Intentionally left empty...
Страница 96: ...Intentionally left empty...
Страница 108: ...Intentionally left empty...
Страница 109: ...105 Appendices Wiring diagrams V 10 Controller electrical diagram Figure 45 Controller electrical diagram...
Страница 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Страница 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...
Страница 113: ...Item Description Part ID Kit Quantity 200 Fan or 240 113 P 311 1 109 Boiler part diagrams SL 26 260 G3...