Note

 

If converting from natural gas to propane, order the propane conversion parts kit (IBC Part # P-802) from your 

authorized IBC distributor.

Use the natural gas conversion parts kit if the fuel source at the site uses natural gas and the modulating water heater 

has been set up  to operate with propane. Check the rating plate on the water heater to see which fuel source the 

particular unit has been set up with.

Using this conversion kit, a qualified technician will need to:

 1.  Perform a fuel conversion.

 2.  Perform a combustion test.

 3.  Fill in the information required on the fuel conversion labels, and affix them to the unit after the conversion is 

completed.

Warning

 

This conversion kit shall be installed by a qualified service agency in 
accordance with the manufacturer’s instructions and all applicable codes and 
requirements of the authority having jurisdiction. If the information in these 
instructions is not followed exactly, a fire, an explosion or production of carbon 
monoxide may result causing property damage, personal injury or loss of life. 

The qualified service agency is responsible for the proper installation of this kit. 
The installation is not proper and complete until the operation of the converted 
appliance is checked as specified in the manufacturer’s instructions supplied 
with the kit.

The unit will automatically de-rate the maximum input at a rate of approximately 2% per 1,000’ above 4,500’. The gas 

valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.

Included with the conversion kit:

1 x Orifice - marked "660" - IBC Part # 180-173

1 x O-ring - IBC Part # 150-175

1 x Rating Plate Fuel Overlay - IBC Part # 080-224A

1 x Gas Valve Conversion Label - IBC Part # 080-107B

1 x Installer Identifier Label - IBC Part # 080-211A

 SFT 28-199 -  Fuel Conversion to Natural Gas 

(LP to NG) Kit P-803

Содержание SFT 28-199

Страница 1: ...e codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing p...

Страница 2: ...ns After converting the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results co...

Страница 3: ...conversion 1 Turn off the gas supply at the gas shut off valve 2 Disconnect the electrical power 3 Disconnect the gas valve harness plug from the gas valve 4 Disconnect the nut at the gas valve outlet...

Страница 4: ...tected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off the uni...

Страница 5: ...will show in the service display a Compare the readings with Table 1 Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typical...

Страница 6: ...t shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 P...

Страница 7: ...SFT 28 199 FuelConversion to NaturalGas LP to NG Kit P 803 7 Where to Place Conversion Labels on the Water Heater...

Отзывы: