![IBC INTERSTAR IWT Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/ibc/interstar-iwt-series/interstar-iwt-series_installation-and-operating-manual_3263322007.webp)
5
Specifications
The table below displays information on dimensions and weights to help with installing and connecting
the tank. Diagrams provided in this section contain connection sizes.
Specification
IWT 40
(150L)
IWT 50
(200L)
IWT 65
(250L)
IWT 80
(302L)
IWT 119
(425L)
Max. Operating Pressure
150 psi
150 psi
150 psi
150 psi
150 psi
Height (inches/mm)
45.2 / 1148
57 / 1448
54.5 / 1384
64.5 / 1638
65.7 / 1669
Diameter (inches/mm)
22 / 559
22 / 559
24.5 / 622
24.5 / 622
28 / 711
Operation at outlet water
temperature ° F / ° C
180 / 82
180 / 82
180 / 82
180 / 82
180 / 82
Gross tank volume -
USG / Liters
40 / 151
53 / 201
66 / 250
79.3 / 300
119 / 450
Net tank volume -
USG / Liters
38.3 / 145
50.7 / 192
63.9 / 242
77.4 / 293
113 / 426
Weight - empty Lbs / kg
100 / 45.3
127 / 57.6
145 / 65.8
166 / 75
230 / 104
Shipping weight -
Lbs / kg
120 / 54.4
145 / 65.7
170 / 77
193 / 87.5
275 /125
Domestic conn. size
¾" M
¾" M
¾"M
1" M
1½" M
First hour delivery - Gal/Hr *
204
259
309
356
474
Continuous Draw @ -
Gal/Hr*
170
217
259
287
373
Boiler Output Required -
Btu/Hr*
120,000
140,000
180,000
200,000
240,000
Minimum flow rate - GPM
14
14
14
14
20
Heating coil pressure drop -
Ft. Hd.*
6.2
7
7.5
10.1
11.8
Coil heat transfer area - Ft.
2
* 8.1
10.2
11.4
13.4
10.2
Certified - water heater
Certified - low lead
Table 1
Dimensions and weights: IWT 40, IWT 50, IWT 65, IWT 80, IWT 119
*Based on 180⁰F boiler supply and 58⁰F entering cold water