7.0 Troubleshooting

This section includes conditions that may occur in the water heater as well as various solutions.

Symptom

Diagnosis

Solution

No hot
water at
faucets

Boiler does
not operate

Ensure boiler power is on.

Ensure the boiler is programed for DHW and the water
temperatures are set properly

Check the tank temperature on the IBC screen, Open or Short +
sensor or wiring issue

Water
Heater
Circulator
does not
operate

Follow steps for Boiler does not operate

Ensure the pump relay is closed and suppling power to the pump

Ensure the zone valve is open and the end switch is closed calling
for heat

Check wiring connections at the circulator

Measure voltage at the circulator during a call for heat, should see
120VAC

If power is at the circulator and connections are correct, replace
circulator

Water heater
zone valve
does not
open

Follow steps for Boiler does not operate

Check for 24VAC at the zone valve while there is a call for heat, if
correct voltage is available and connections are good, replace the
zone valve.

Tank sensor
open, short,
or mis-wired

Ensure the tank sensor is connected to the correct terminals and
the wires are properly attached to the terminal strip and the sensor
is properly attached to the wiring at the tank

Disconnect the sensor wires from the terminal strip and measure
the resistance in Ohms across the 2 sensor wires. Compare this
value to the chart and the actual tank temperature. Repeat this test
for the sensor only and compare the results.

Check/replace the wire from the boiler to the sensor or replace the
sensor

Water at
faucets too
cool

DHW
temperature
setting too
low

Increase the DHW Tank Set Point temperature

Boiler
Maximum
Supply
Temp.
setting too
low

Make sure the Maximum Supply Temp. setting is at least 10°F higher than
the DHW Supply Setpoint PLUS 1/2 of the Supply Diff’l Temp setting.

Содержание INTERSTAR IWT Series

Страница 1: ...0 IWT 119 CAUTION The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or Class of 1 as listed in Clinical Toxicology of Commercial Products 5th edition The pressure...

Страница 2: ...jury to occupants and in extreme cases to death Keep instructions near the water heater for future reference When using electrical appliances follow safety precautions to reduce the risk of fire elect...

Страница 3: ...Installation checklist 15 2 2 System zone control 16 2 3 Priority or non priority for hot water 17 2 3 1 Option 1 Priority 17 2 3 2 Option 2 Non priority 17 2 4 Locating the water heater 18 2 5 Temper...

Страница 4: ...5 2 Start up 27 5 3 Temperature adjustment 27 6 0 Maintenance 29 6 1 Chemical cleaning of the heating coil 29 6 1 1 Flushing the tank 29 6 1 2 Refilling the tank 30 7 0 Troubleshooting 31 8 0 Diagram...

Страница 5: ...n experienced skilled installer or service agency The water heater contains very hot water under high pressure Do not unscrew any pipe fittings or attempt to disconnect any components of this water he...

Страница 6: ...lass of 1 as listed in clinical Toxicology of Commercial Products latest edition Installation start up and servicing of IBC boilers and water heaters must be done with due care and attention and shoul...

Страница 7: ...Liters 40 151 53 201 66 250 79 3 300 119 450 Net tank volume USG Liters 38 3 145 50 7 192 63 9 242 77 4 293 113 426 Weight empty Lbs kg 100 45 3 127 57 6 145 65 8 166 75 230 104 Shipping weight Lbs k...

Страница 8: ...111 419 Weight empty Lbs kg 188 85 246 111 Shipping weight Lbs kg 201 91 290 131 Domestic conn size 1 M 1 M First hour delivery Gal Hr 719 753 Continuous Draw Gal Hr 653 653 Boiler Output Required Bt...

Страница 9: ...ht inches mm 45 2 1148 57 1448 54 5 1384 B Diameter inches mm 22 559 22 559 24 5 622 M NPT Hot water outlet M NPT Cold water outlet F NPT T P relief valve 1 M NPT In from boiler boiler supply Sensor w...

Страница 10: ...Hot water outlet 1 M NPT Hot water outlet 1 M NPT Hot water outlet 1 M NPT In from boiler boiler supply 1 M NPT In from boiler boiler supply 1 M NPT In from boiler boiler supply 1 M NPT In from boiler...

Страница 11: ...000 166 131 204 170 140 000 166 131 204 170 160 000 166 131 204 170 Table 3 Recovery rates IWT 40 IWT 50 135 F Boiler Output BTU Hr Boiler Flow 14 gpm 160 F Boiler Flow 14 gpm 180 F 1st Hour Rating G...

Страница 12: ...000 244 192 300 249 180 000 252 199 309 259 Table 5 Recovery rates IWT 65 IWT 80 135 F Boiler Output BTU Hr Boiler Flow 14 gpm 160 F Boiler Flow 14 gpm 180 F 1st Hour Rating Gal Hr Continuous rating...

Страница 13: ...3 280 200 000 344 240 413 311 220 000 367 263 443 342 240 000 390 287 474 373 Table 7 Recovery rates IWT 119 IWT 80 Max 135 F Boiler Output BTU Hr Boiler Flow 25 gpm 160 F Boiler Flow 25 gpm 180 F 1st...

Страница 14: ...405 299 479 373 250 000 418 311 494 389 300 000 479 373 570 467 350 000 539 435 646 544 380 000 576 473 692 591 400 000 600 498 722 622 420 000 625 523 753 653 Table 9 Recovery rates IWT 119 Max Press...

Страница 15: ...art HLW 101 2 Section IV of the ASME Boiler and Pressure Vessel Code all IBC InterStor IWT series indirect water heater products are exempt from compliance with the code Check with local codes for app...

Страница 16: ...For more information see Temperature and pressure relief valve on page 18 1 3 Conformity Inspect shipment carefully for signs of damage All equipment is carefully inspected and packed IBC s responsib...

Страница 17: ...t a time Increase the tank size if these factors are present Carefully review the IBC water heater Specifications on page 5 and consult ASHRAE sizing guides and other reliable references Dimensions we...

Страница 18: ...be sized for the minimum flow rate with all the zones in use and a maximum flow with only the water heater in use The best method for zone control is the use of circulators The three most common syste...

Страница 19: ...priority for hot water 2 3 1 Option 1 Priority The demand for space heating is interrupted until the hot water demand is satisfied This option provides the maximum delivery of hot water You can easil...

Страница 20: ...Surface Distance from Combustibles For Service Front 1 24 Rear Right and Left Sides 1 1 Top 1 1 Bottom 0 0 Table 12 Clearances from heater jacket 2 5 Temperature and pressure relief valve 1 Supply a...

Страница 21: ...stem having a back flow preventer in the cold water supply line the installation of a thermal expansion tank is required 6 Refer to Figure 8 for suggested external components 2 7 Removing the existing...

Страница 22: ...orm to all applicable codes Caution Do not operate the IBC water heaters in areas where the water pH is above 8 0 or below 6 0 and or with chloride concentrations greater than 80 parts per million ppm...

Страница 23: ...onnect to cold water supply connection using the following suggested components where applicable a union a heat trap a shut off valve a drain valve an expansion tank a back flow preventer and a vacuum...

Страница 24: ...uidance 2 It is recommended that minimum size 1 pipe be used on the water heater zone to ensure adequate flow larger sizes min 1 Note The piping drawings in Section 8 0 are simple guides to a successf...

Страница 25: ...d 1 full port zone valves with a high CV on the water heater zone to ensure adequate flow The water heater connection labeled In from Boiler must be piped to the boiler supply piping after the air pur...

Страница 26: ...nsed environment and compare with the value derived from the measurement of the resistance obtained by connecting a good quality test meter capable of measuring up to 5 000 k 5 000 000 at the controll...

Страница 27: ...754 55 13 17 436 140 60 2 490 60 16 15 311 145 63 2 255 65 18 13 474 150 66 2 045 70 21 11 883 155 68 1 857 75 24 10 501 160 71 1 689 80 27 9 299 165 74 1 538 85 29 8 250 170 77 1 403 90 32 7 334 175...

Страница 28: ...angle to the back of the control 2 Loosen the mounting screw and carefully insert the sensing bulb into the well until the control mounts to the well head 3 Tighten the screw to lock in place 4 Conne...

Страница 29: ...to place the boiler in operation 5 3 Temperature adjustment The tank sensor controls the maximum water temperature in the water heater If it is set too high the resulting hot water can cause painful s...

Страница 30: ...Turn the faucet on full and allow it to run long enough to ensure the water and piping have been heated up to the discharge temperature of the tank Using an accurate thermometer test the water tempera...

Страница 31: ...s a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference between the boiler supply and return lines and a reduced recovery rate R...

Страница 32: ...olution to set in the tank for 30 minutes 11 Drain the tank completely using fittings and hoses as required to reach a drain 6 1 2 Refilling the tank 1 Fill the water heater tank with fresh cold water...

Страница 33: ...valve does not open Follow steps for Boiler does not operate Check for 24VAC at the zone valve while there is a call for heat if correct voltage is available and connections are good replace the zone...

Страница 34: ...Tank Set Point temperature DHW temperature sensor giving false reading Sensor is not fully inserted into the well Sensor giving incorrect resistance reading Sensor connected to IBC Therm terminals ins...

Страница 35: ...components may operate when other loads are running at a higher priority resulting in cold air blowing or taking heat from another load You may need to modify the wiring to separate these functions fr...

Страница 36: ...Figure 6 Primary secondary piping Figure 7 Two sided parallel piping on indirect side primary secondary on heating side 34 Section Diagrams...

Страница 37: ...discharge pipe field supplied always required Drain pan Potable expansion tank required where backflow check valves are installed Whole house water filter required where contaminants are present in th...

Страница 38: ...aker in the position shown with no shut off valves between the device and the tank Important Note All external components shown are field supplied IBC supplies the tank including the factory installed...

Страница 39: ......

Страница 40: ...77 0277 T 856 877 0544 F 604 877 0295 F 856 735 5584 Toll Free 1 844 HEAT IBC 1 844 432 8422 www ibcboiler com Information in this document is subject to change without notice IBC assumes no responsib...

Отзывы: