![IBC INTERSTAR IWT Series Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/ibc/interstar-iwt-series/interstar-iwt-series_installation-and-operating-manual_3263322011.webp)
Recovery rate
IWT 40 (135 °F)
Boiler
Output
(BTU/Hr)
Boiler Flow = 14 gpm / 160 °F
Boiler Flow - 14 gpm / 180°F
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F
entering cold water
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F
entering cold water
50,000
97
60
114
78
60,000
108
72
129
93
80,000
132
96
159
124
100,000
155
120
190
156
120,000
166
131
204
170
140,000
166
131
204
170
160,000
166
131
204
170
Table 3
Recovery rates - IWT 40
IWT 50 (135 °F)
Boiler
Output
(BTU/Hr)
Boiler Flow = 14 gpm / 160 °F
Boiler Flow - 14 gpm / 180°F
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F
entering cold water
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F
entering cold water
50,000
107
60
124
78
60,000
118
72
139
93
80,000
141
96
169
124
100,000
165
120
199
156
120,000
188
144
230
187
140,000
211
167
259
217
160,000
211
167
259
217
Table 4
Recovery rates - IWT 50