8.3.2 Temperature issues
Temperature issues
Issue
Diagnosis
Fix
Low heat
Operating temperature too low.
Increase temperature target.
Increase temperature target.
Priority parameters or load
configuration improperly set up.
Review load configuration parameters.
appliance undersized.
Refer to Load Calculation vs. Boiler Output.
Air trapped within system.
Bleed system as required.
Improper system piping.
Refer to recommended piping guidelines for
the respective boiler model.
System pump undersized.
Check pump manufacturer’s data/check
temp differential across heat exchanger.
Poor gas:air mixing.
Check CO
2
level.
Defective thermostat.
Refer to manufacturer’s instructions.
Obstruction in condensate
drain.
Inspect and clean condensate drain.
appliance cycling on operating/
safety controls.
Check operation with Ohmmeter/Voltmeter.
System radiation undersized.
Check manufacturer’s rating tables for
capacity per foot.
Temperature
exceeds thermostat
setting
Incorrect anticipator setting.
Check with Ammeter.
Thermostat not level.
Check level.
One or more zones
do not heat properly
Air trapped within zone(s) piping Vent system/zone as required.
Low radiation/ excessive heat
loss.
Check actual length of pipe using radiation /
heat loss calculation.
Low flow rate to zone(s).
Check temperature drop across zone.
Defective zone valve/ zone
circulator.
Check operation per manufacturer’s
instructions.
93
8.3.2 Temperature issues
Содержание IBGFSW1-0110
Страница 8: ...Intentionally left empty ...
Страница 14: ...Intentionally left empty ...
Страница 52: ...Figure 36 Two pump two load parallel piping concept 48 Section Installation ...
Страница 74: ...Intentionally left empty ...
Страница 100: ...Intentionally left empty ...
Страница 101: ...97 Appendices Wiring diagrams Figure 48 Controller electrical diagram ...
Страница 102: ...Figure 49 Internal wiring diagram 98 Section Appendices ...
Страница 103: ...Figure 50 Sequence of Operation 99 Appendices ...
Страница 106: ...102 Section Appendices ...