8.3 Miscellaneous touchscreen controller errors
Miscellaneous errors
Issue
Diagnosis
Fix
“ Loop/Indoor Sensor”
“Insufficient Air Flow”
“Insufficient Water Pressure”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back of
the controller board.
“Unknown Error”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back of
the controller board.
Temperature
sensor input
problem.
Test each temperature
sensor for appropriate
readings and Replace
defective temperature
sensor.
Error - Max. Inlet/Outlet Sensor Temp. Exceeded. >
Check water flow Water temperature signal not
within acceptable range. Potential flow or sensor
failure. Consult service technician.
Current outlet
temperature
exceeds
operating limit.
Check water flow.
Defective or
disconnected
temperature
sensor.
Check wiring to
temperature sensor and
control module.
Check temperature sensor.
Blank – screen dark, but fan running Indicative of
power-surge damage to appliance
Check transformer; replace
if damaged.
Check circuit board for
visible damage.
Controller is stuck in "service" mode after software
update.
If update fails
or no updates
applied.
Restarting returns the
boiler to normal operation.
91
8.3 Miscellaneous touchscreen controller errors
Содержание IBGFSW1-0110
Страница 8: ...Intentionally left empty ...
Страница 14: ...Intentionally left empty ...
Страница 52: ...Figure 36 Two pump two load parallel piping concept 48 Section Installation ...
Страница 74: ...Intentionally left empty ...
Страница 100: ...Intentionally left empty ...
Страница 101: ...97 Appendices Wiring diagrams Figure 48 Controller electrical diagram ...
Страница 102: ...Figure 49 Internal wiring diagram 98 Section Appendices ...
Страница 103: ...Figure 50 Sequence of Operation 99 Appendices ...
Страница 106: ...102 Section Appendices ...