Temp. °F/°C
Resist.
Ω – Ohm
Temp. °F/°C
Resist.
Ω – Ohm
0 / -18
85,362
100 / 38
5,828
5 / -15
72,918
105 / 41
5,210
10 / -12
62,465
110 / 43
4,665
15 / -9
53,658
115 / 46
4,184
20 / -7
42,218
120 / 49
3,760
25 / -4
39,913
125 / 52
3,383
30 / -1
34,558
130 / 54
3,050
35 / 2
29,996
135 / 57
2,754
40 / 4
26,099
140 / 60
2,490
45 / 7
22,763
145 / 63
2,255
50 / 10
19,900
150 / 66
2,045
55 / 13
17,436
155 / 68
1,857
60 / 16
15,311
160 / 71
1,689
65 / 18
13,474
165 / 74
1,538
70 / 21
11,883
170 / 77
1,403
75 / 24
10,501
175 / 79
1,281
80 / 27
9,299
180 / 82
1,172
85 / 29
8,250
185 / 85
1,073
90 / 35
7,334
190 / 88
983
95 / 35
6,532
195 / 91
903
Table 12
Temperature sensor resistance values - 10K ohms
8.1.2 Fan
The fan is controlled via the SIM+ control. The SIM+ provides electronic commutating power to the
fan motor coilers determining the fan speed and power usage.
8.1.3 Water pressure sensor
The water pressure sensor ensures that there is adequate pressure in the heating system for safe
operation. The pressure is displayed in PSI as the default. If the system pressure should drop
below 8PSI the firing rate of the boiler is reduced. If the pressure drops to 4PSI or lower, the boiler
will not fire.
86
Section: Troubleshooting
Содержание IBGFSW1-0110
Страница 8: ...Intentionally left empty ...
Страница 14: ...Intentionally left empty ...
Страница 52: ...Figure 36 Two pump two load parallel piping concept 48 Section Installation ...
Страница 74: ...Intentionally left empty ...
Страница 100: ...Intentionally left empty ...
Страница 101: ...97 Appendices Wiring diagrams Figure 48 Controller electrical diagram ...
Страница 102: ...Figure 49 Internal wiring diagram 98 Section Appendices ...
Страница 103: ...Figure 50 Sequence of Operation 99 Appendices ...
Страница 106: ...102 Section Appendices ...