INSTALLATION AND OPERATION INSTRUCTIONS
1-10
DC SERIES COMBI BOILERS
DC 23-84, DC 29-106, DC 33-124, DC 33-160
•
The elevation of both pipes can be raised in “periscope style” after passing
through the wall, then configured as in
Figure 8,
to gain required clearance.
•
Use a 45° elbow on the exhaust termination to launch the plume up and off
the sidewall, for protection of wall.
•
Bird screen of 1/4" stainless steel or plastic mesh eg. (IPEX System 636 drain
grate for CPVC systems) is useful to guard against foreign objects.
DIRECT VENT CONCENTRIC SIDE WALL TERMINATION
The following Concentric Side Wall Termination Kits are approved for use with
the DC series boilers and are subject to the following restrictions.
NOTE:
Some
jurisdictions may not allow this type of side wall termination due to close proximity
to the neighboring properties.
See Figure 9 and 10 on page 1-11.
Do not use Concentric Side Wall Termination Kits when the outdoor design
temperature is below 5°F / -15°C. The possible blockage of the combustion air
intake increases when the outdoor temperature drops below this temperature.
The installation instructions, clearances and wall thickness requirements of the
approved vent termination manufactures must be followed.
Approved Concentric Side Wall Termination Kits are listed as follows: (Alternate
vent termination kits must be submitted to IBC for approval prior to installation.)
•
Duravent – Polypro #3PPS-HK – Horizontal Termination Kit – Concentric
•
Centrotherm – Innoflue #ICWT242 (2" termination) + ICTC0224 (2" transition
to 2 pipe)
•
Centrotherm – Innoflue #ICWT352 (3" termination) + ICTC0335 (3" transition
to 2 pipe)
•
Ipex - # 197009 – 3” CPVC
Figure 8: Sidewall vent termination - piping configuration
WARNING
It is extremely important to
maintain at least the minimum
separation of exhaust vent
termination from boiler intake
air as illustrated in figures
5, 8 and 13. Failure to do so
can result in a dangerous
situation where exhaust
gasses are re-ingested with
combustion air. Damage to
the boiler can result from
a failure to maintain these
separations. Improper
installation will void the
warranty.
WARNING
In areas of high snowfall,
Users must be advised to
check side wall vent and
air intake terminations on
a regular basis to ensure
blockage does not occur.