CONTROL UNIT FOR ROTATING HEAT EXCHANGER
MicroMax
Article no. F21009201
Страница 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax Article no F21009201...
Страница 2: ......
Страница 3: ...5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Push button 9 Connection diagram 10 Connections 10 Checks before powering up the control u...
Страница 4: ...et Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw ma...
Страница 5: ...power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains in...
Страница 6: ...C Directive 2004 108 EC All control units are approved according to the requirements of the EMC Directive 2004 108 EC and are tested according to standard EN 61800 3 2004 emission category C1 and immu...
Страница 7: ...peed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that wheel speed is proportional to the input signal from the cont...
Страница 8: ...wer input max 210 W Input current max 0 9 A External fuse max 10 A Output voltage 3x0 230 V Minimum frequency Fixed 4 Hz Max frequency 40 100 Hz Motor output max 90 W Motor current 0 7 A Exact value c...
Страница 9: ...is set to OFF Low speed The wheel rotates at the fixed minimum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Manual operation test mode OPERATIONAL INDICATIO...
Страница 10: ...normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms and trips if the con...
Страница 11: ...fter 4 5 seconds The motor is too small in relation to rotor diameter Wheel rotation sluggish Damaged motor e g bearing fault Measure amperage NOTE Precise voltages and amperages can only be obtained...
Страница 12: ...hould be used to protect the motor from overheating Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max...
Страница 13: ...Set the High Speed DIP switch to the ON position Adjust Max speed so that the wheel rotates at 10 12 rpm or as per directions from wheel manufacturer After a test run set the DIP switch to OFF Checkin...
Страница 14: ...GLAND Motor cable lflex Classic 110 CY 7G0 5 Shielded Incoming EKK 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...
Страница 15: ...YOUR NOTES 13...