Manual
Issue 1.5
87
11.3
Digital inputs
Digital inputs
Number
8
Version
Galvanically isolated, protected against reverse polarity, single
ended
Input signal
24 V DC
Max. input voltage
±60 V permanent
Signal level log. 0
Signal level log. 1
> -6 V; < +6 V
< -10 V; > +10 V
Input current
1 mA, constant
Debounce filter
Optional with 4 operating modes
Sampling rate
Max. 40 kHz, freely adjustable
Delay
typ. 10 µs
Electrical isolation
Channel-channel
Channel-housing
2.5 kV AC
2.5 kV AC
Connector type
16-pin connector, connector with clamp-type terminals (0.2 mm
2
to 2.5 mm
2
), can be screwed, included in delivery