background image

ibaPADU-16-M Manual 
 

8.6 

Analog Connector Pinning (X2-X5) 

 

 

Note 

In case of request for spare parts for HARTING connectors please contact the support 
of iba AG. 

 

Different connector terminals are used (depends on the input signals): 

 

X5:  Input ±10 V  

 

Low voltage input terminal. 
  
All low voltage inputs are wired herein 
- each signal with +; -;  
shield optional.  
 
This connector is always present.

 

 

 

Issue 2.1 

21

 

Содержание ibaPADU-16-M

Страница 1: ...ibaPADU 16 M Modular Parallel A D Converter Unit for High Speed Measurement Manual Issue 2 1...

Страница 2: ...guaranteed However the information in this publication is updated regularly Required corrections are contained in the following regulations or can be downloaded on the Internet The current version is...

Страница 3: ...1 M Mode 13 7 2 F Mode 13 7 3 Process Monitoring Topology Example Simultaneous sampling 14 8 Product Properties 16 8 1 Sub modules 17 8 1 1 Analog Inputs 10 V DC 17 8 1 2 Analog Inputs 110 V AC 220 V...

Страница 4: ...1 Input Gain 26 9 2 2 Programmable Low Pass Filter 26 9 2 3 Calibration Parameters 28 10 Configuring with ibaPDA 29 10 1 Configuring ibaPADU 16 M with M mode 29 10 2 Configuring Triggers 34 10 3 Conf...

Страница 5: ...the standard regulations He or she must have the following qualifications Trained and authorized to energize de energize clear ground and tag circuits and equipment in accordance with established safe...

Страница 6: ...r machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The non observance of this s...

Страница 7: ...ales contract contains the entire obligation of iba The warranty contained in the contract between the parties is the sole warranty of iba Any statements contained herein do not create new warranties...

Страница 8: ...ent during operation Non observance of the safety instructions can result in severe personal injury or property damage It is especially important that the warning information in all of the relevant Op...

Страница 9: ...p to two modules can be used Up to 4 rugged HARTING connectors depending to the used analog input types and the amount of channels The device is housed in a rugged 19 rack mount chassis All connectors...

Страница 10: ...er of connectors and the types of inserts will vary based on the types of mod ules ordered for the ibaPADU 16 M For 10 V inputs 72 pin female insert For 110 V inputs 40 pin female insert For current i...

Страница 11: ...tware ibaScope ibaPDA V6 5 2 Hardware One of the following fibre optic boards ibaFOB io S only for one module ibaFOB 4i S and ibaFOB 4o ibaFOB io D or ibaFOB io Dexp only for one module ibaFOB 2io D o...

Страница 12: ...al input connectors before operating the V 24 Service port 6 3 Modules exchange The device must be opened if modules are to be changed The device may be opened ONLY by qualified personnel Remove power...

Страница 13: ...t links All device samples are fully synchronized with ns ac curacy 7 2 F Mode The ibaPADU 16 M device needs only 2 simple fiber optic connections per device to the FOB card The device mode switch mus...

Страница 14: ...n be sampled continuously using this topology with one ibaFOB 4i 4o For continuous process monitoring multiplex operation of the device network is not required All devices must have the address switch...

Страница 15: ...t Recorder TFR Devices are organized in n rings one device fully connected needs 2 rings max 2 devices per ibaFOB 4i 4o S or D All devices must have the address switch on position 0 M mode Devices Onl...

Страница 16: ...B Each sub device has 3 LEDs Run Link Error A fiber optic input and output to transmit the signals or for daisy chaining of multiple devices in F mode 8 slots for 1 8 analog inputs 16 bits depending...

Страница 17: ...Inputs 110 V AC 220 V AC 380 V AC These inputs transform these values into 10 V DC ranges of the measuring circuitry and are designed for the direct connection of the voltage transducers Each 4 of the...

Страница 18: ...ws the values that have to be set by the software as signal input range Module Name 1st Input Range 2nd Input Range ibaMX 1 AI 10V 10 V ibaMX 1 AI 110VAC 312 V ibaMX 1 AI 220VAC 624 V ibaMX 1 AI 380 V...

Страница 19: ...rror Mode switch Module A LEDs run link error Mode switch Module B Rear View Analog inputs X2 High Voltage current inputs ModA 0 3 X3 High Voltage current inputs ModA 4 7 X4 High Voltage current input...

Страница 20: ...ft 2 m 8 4 Fiber Optic Inputs X8 and X11 and Outputs X9 and X12 The 2 connectors ST type for each module serve to connect the device to the fiber optic bus 8 5 Device Mode Setting with Switches S1 and...

Страница 21: ...rts for HARTING connectors please contact the support of iba AG Different connector terminals are used depends on the input signals X5 Input 10 V Low voltage input terminal All low voltage inputs are...

Страница 22: ...074 V or High Voltage 110 V 250 V 380 V 1074 V input terminal Max 4 signals per terminal This con nector is present only if high voltage in put modules were chosen in groups of 4 This terminal may be...

Страница 23: ...erminals Which short circuit the signal pins whenever the jack is disconnected Max 4 signals per terminal This connector is present only if current input modules were chosen in groups of 4 This termin...

Страница 24: ...on request 8 8 LED Indicators for Modules A and B Run Link and Error LED Status Description L1 Run green Blinking Off Power is on and device is ready for operation Insufficient power or device failure...

Страница 25: ...ing new firmware Important note In normal operation mode the V 24 cable must not be connected 8 10 Shield Connector N1 for Physical Earth Proper connection of cable shielding to the device should be e...

Страница 26: ...log Modules 9 2 1 Input Gain Input gain is set to 0 dB gain factor 1 Confirmation of setting by responding of de vice to the FOB Card is given 9 2 2 Programmable Low Pass Filter A programmable 72 dB 6...

Страница 27: ...grams show the characteristic of the used programmable input filter The filter itself causes a delay within the ibaPADU This delay is named Group delay At an edge frequency of 1 kHz this delay is appr...

Страница 28: ...0 Hz Reflected frequency band starts at 50 Hz x 100 Hz 5000 Hz A signal frequency of 5100 Hz would be noticeable at 100 Hz Example 2 fc 1000 Hz Reflected frequency band starts at 50 Hz x 1000 Hz 50 00...

Страница 29: ...elect Configure I O Man ager in the main menu Configure the ibaPADU 16 M interface in following steps 1 If several iba PCI cards are used in ibaPDA set the board connected to ibaPADU 16 M to the inter...

Страница 30: ...correctly with two bidirectional fibre optic links two modules of the Padu 16 M A and B are defined on the connected links You see the communication status OK in the Info tab of the connected links No...

Страница 31: ...ule that allows the user to define the name unit and scales of this submodule The standard submodules in the select box refer to the modules described in chap ter 8 1 6 After adding the eight submodul...

Страница 32: ...must set the other link to not connected FOB M Link timebase Set the time to a value between 40 s and 2000 s Note The Link timebase is valid for all other links that work in M mode The module timebase...

Страница 33: ...e parameters manually It is possible to define signal comments by clicking the button at the end of the name field You can also display other signal properties in the grid with a right mouse click on...

Страница 34: ...signals Each digital signal is a trigger Instead of the normal expression builder the trigger module uses a special trigger builder dialog to create the expressions for the triggers The trigger builde...

Страница 35: ...is an extra custom function where you can build your own expres sion The custom tab contains the regular expression builder Finish the definition of one trigger event with OK Define further trigger e...

Страница 36: ...then the trigger pool fires The trigger can fire on a rising edge of the trigger signals or it can fire each sample the trigger signal is 1 If you want to use a trigger pool as a trigger then you hav...

Страница 37: ...1 Activate and name the data store 2 Define the Start Stop Trigger Either as a single trigger event or one or more events from the trigger pool see above 3 Define the signals to store 4 Define the dat...

Страница 38: ...you are in the ibaPDA client main view Mainly ibaPDA has three view types The trend graph the Scope view and the FFT view Click to the icons to create the views in the signal monitor and place the doc...

Страница 39: ...idity 95 no condensation Coldness and dry heat Acc DIN EN 60068 2 1 DIN EN 60068 2 2 Rel humidity heat Acc DIN EN 60068 2 30 Temperature change Acc DIN EN 60068 2 14 Other environmental conditions Acc...

Страница 40: ...n Protection Class IP20 FO cable Coupling 62 5 125 m ST Lean Maximum length of fiber optics between devices 1 24 mi 2000 m Product Safety according to EN 61010 1 1CATII 250 V AC Power supply 115 V AC...

Страница 41: ...ilter twice 3 dB 20 kHz Filter Frequency range 75 Hz to 12 500 Hz 80 dB 75 Hz to 12 500 Hz 80 dB 75 Hz to 12 500 Hz 80 dB 75 Hz to 12 500 Hz 80 dB Input level type Nom Range Max 10 V DC 10 DC V 100 V...

Страница 42: ...equency range 75 Hz to 12 500 Hz 80 dB 75 Hz to 12 500 Hz 80 dB 75 Hz to 12 500 Hz 80 dB Input level type Nom Range Max 1 A AC 0 A to 6 25 A DC 100 A DC for 1s 100 A DC for 1 s 100 s pause 5 A AC 15 A...

Страница 43: ...26000 17 126100 Number of inputs 8 8 Input level Nom Overload 24 V DC 300 V DC 1 min 110 V to 125 V DC 300 V DC 1 min log0 6 V log1 10 V log0 30 V log1 40 V Input current 1 mA 1 mA Sampling rate 25 kH...

Страница 44: ...specify the serial number iba S N of the product Contact Headquarters iba AG Koenigswarterstr 44 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 E Mail iba iba ag com Contact Mr Harald O...

Отзывы: