N700E INSTRUCTION MANUAL
2-33
2.3.9 Run Command Source to Remote Operator, RJ-45 Modbus
(Except 300LF~750LF)
Diagram
Programming N700E Parameters
Executing Run Command
Diagram
Programming for Frequency Command Source to RJ 45
On Keypad, program following Parameters with corresponding set point:
Code
Set Value Description
A02
2
Run Command by Remote RJ 45
b17
1
Communication node (1 ~ 32)
Running/Stopping VFD
Use Modbus register 2
Data: 0 = Stop, 1 = Forward Run, 2 = Reverse Run
2.3.10 Run Command Source to Remote Operator (RXP-RXN)
Use RXP, RXN Terminal
Programming N700E Parameters
Running/Stopping VFD
Programming Frequency Command Source to Remote Operator, RXP - RXN
On Keypad, program following Parameters with corresponding set point
Code
Set Value
Description
A02
3
Frequency Command by Remote (RXP-
RXN)
b31
3
RXP-RXN terminal Communication baud
rate(9600bps)
Running/Stopping VFD
Use Modbus register 2
Data: 0 = Stop, 1 = Forward Run, 2 = Reverse Run
Pin No.
Signal Descriptions
1
2
3
RS - 485+
4
5
6
RS - 485-
7
24V
8
24V GND