User manual
5
1~1.5
m
of
distance
from
the
generator
set
and
1.5~2m
above
the
generator
set.
◆
The
generator
set
working
room
shall
be
furnished
with
fire
extinguish
hydrant
which
conform
to
the
specified
standard.
◆
Emergency
lighting
facilities
shall
be
installed
in
the
generator
set
working
room
for
the
convenience
of
operation
and
maintenance.
◆
No
combustible
and
explosive
materials
are
allowed
to
be
placed
in
the
generator
set
working
room.
Below
is
the
layout
for
the
open
system
generator
set
working
room.
(Foundation
drawing
Refer
to
APPENDIX
B
)
Note:
Our
company
can
make
drawings
and
design
installation
dimensions
for
generator
set
working
room
according
to
customer’s
special
requirements.
Below
is
the
layout
for
the
canopy
system
generator
set
working
room.
(Foundation
drawing
Refer
to
APPENDIX
C
)
Note:
Canopied
generator
set
can
work
outdoor
directly.
If
users
wants
to
operate
the
generator
set
indoor,
above
diagram
can
be
taken
as
reference.
we
can
design
the
layout
of
generator
set
working
room
and
installation
dimension
according
to
customer’s
special
requirements.
2.5
Installation
of
Generator
Set
2.5.1
Locate
the
position
of
generator
set
Vibration
reduction
units
have
been
installed
on
our
generator
sets
(except
a
few
generator
sets
don’t
have
this
kind
of
facility).
Users
can
take
reference
on
the
installation
diagram,
correctly
install
the
generator
set
on
a
flat
and
hard
foundation,
use
the
expansion
bolts
to
tightly
fix
the
generator
set
to
the
concrete
foundation
through
the
installation
holes
on
the
base
frame.
When
no
special
requirement
is
needed,
we
don’t
suggest
customers
to
install
additional
vibration
reduction
units.
Soft
connection
is
needed
to
connect
the
parts
of
the
generator
set
to
outside.
For
example:
corrugated
vibration
reduction
pipe
has
been
used
to
connect
exhaust
pipes,
air
exhaust
path,
fuel
inlet
pipe,
fuel
return
pipe
and
busbar
cable
etc.,
all
of
these
parts
need
to
use
soft
connections.
Only
in
this
way
we
can
reduce
the
adverse
effect
caused
by
the
vibration
of
generator
set
to
the
minimum
extent.
2.5.2
Ventilation
When
a
generator
set
with
a
complete
set
of
radiator
assembly
has
been
installed
in
the
working
room,
the
basic
principle
is
to
discharge
the
hot
air
in
the
working
room
to
outside
and
let
in
the
low
temperature
air
from
outside,
and
try
you
best
to
avoid
the
hot
air
come
in
from
outside.
The
diagram
in
the
right
side
demonstrates
the
ideal
position
of
a
generator
set
in
the
working
room.
The
purpose
of
this
arrangement
is
to
get
cold
air
from
the
lowest
point
as
much
as
possible,
and
force
them
to
pass
through
the
radiator
core,
and
then
lead
them
out.
Users
can
use
metal
plate
or
canvas
to
make
a
wind
guide
cover,
the
connection
between
wind
guide
cover
and
the
radiator
shall
be
soft
connection,
so
that
to
cut
off
the
transmission
of
vibration
from
the
generator
set,
and
also
ensure
the
hot
air
exhaust
to
outside
thoroughly.
The
effective
circulation
sectional
area
inside
of
the
wind
guide
cover
shall
be
bigger
than
1.25
times
of
the
front
face
area
of
the
radiator
core.
And
the
wind
guide
cover
shall
be
smooth,
no
sharp
angle
and
camber
so
that
to
reduce
the
resistance
to
the
wind.
At
the
same
time,
the
effective
circulation
sectional
area
in
the
air
inlet
opening
shall
also
be
bigger
than
1.25
times
of
the
front
face
area
of
the
radiator
core.
When
the
users
have
installed
mesh
cover
or
shutters
in
the
air
inlet
/outlet
opening
or
there
is
too
many
cambers
in
the
air
inlet/outlet
opening,
the
effective
air
circulation
sectional
area
will
be
reduced
and
resistance
will
increase,
and
therefore,
it’s
necessary
to
further
increase
air
circulation
area.
Содержание DHY34KSE
Страница 2: ...DIESEL GENERATOR Models Hyundai Engine Series Operation and Maintenance manual ...
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ...APPENDIX E 1 ...
Страница 40: ...2 ...
Страница 41: ...3 ...
Страница 44: ...APPENDIX H ...
Страница 45: ......