1. Technical Specifications
Product type High bay microwave DALI sensor (tri-level control)
Operating voltage 120~277VAC 50/60Hz
Switched power Maximum 20pcs DALI devices, Maximum 40mA
Power consumption < 0.5W
Detection angle 360
o
Detection area (Max.)*
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2 ~ 500Lux, Disable
Warming up time 20s
Operating temperature -20
o
C ~ +50
o
C
IP rating IP65
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
8
HIGH BAY MICROWAVE DALI SENSOR HMW35
Installation and Instruction Manual
Rotary switch preset (Please
see the location in 2. Installation)
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%
5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s
10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%
Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
4. Functions
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a
light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion
hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically
whenever artificial light is unneeded (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light
is sufficient.
4.1 Tri-level Control (Corridor Function)
4.2 Lux Off Function
HMW35-20180529-A2
2. Installation
Warnings:
1. Installation of the sensor involves connecting it to the mains supply. This work must be
carried out by a specialist in accordance with electrotechnical regulations.
2. Disconnect supply before installing.
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100%
or POWER 80% is pressed.
4.3 Load Indication
A. Ceiling mount
B. Screw to the Luminaire by conduit
24.5
91.5
59.3 57.3
47.5
4.1
80.7 75
4.1
66.6
81.5
59.6
66.6
89.9
0.825”
75
64
59.3
57.3
35.2
47.5
84.5
59.3
ぶ
29
163.2
66.6
75
33.7
15
28.5
4.5
ぶ
4.5
59.6
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Installation rack
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
C. Attach to the shade by clamp
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Angle adjustment
Luminaire clamp
Note:We recommend the mounting distance between sensor to sensor
should be more than 2m to prevent sensors from false-triggering.
Installation Height : 20m (forklift) 15m (person)
Detection Range (Ø) :20m