1. Technical Specifications

Product type                                  High bay independent DALI sensor (tri-level control)
Operating voltage                          220-240VAC  50/60Hz
Switched power                            Maximum 20pcs DALI devices, Maximum 40mA
Power consumption                       < 1W
Detection angle                             360

o

Detection area (DxH)                      18 x 15m (Maximum)
Detection range                             10% / 50% / 75% / 100%
Hold time                                       2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time                                0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞  
Stand-by dimming level                  10% / 20% / 30% / 50%
Daylight threshold                           2 ~ 500Lux, Disable
Warming up time                            30s
Operating temperature                    -35

o

C ~ +50

o

IP rating                                         IP65 
Sensor mode                                 HF, PIR, HF+PIR, HF / PIR           

3. Rotary Switch Settings

A rotary switch is built inside the sensor for 
scene selection / fast programming. Total 
16 channels available:

Note: settings can also be changed by remote control HRC-11. The last action controls.

HIGH BAY DUAL SENSE INDEPENDENT DALI SENSOR HIM35

Installation and Instruction Manual 

Rotary switch preset (Please 
see the location in 2. Installation)

Detection 

range 

Channel

0
1
2
3
4
5
6
7
8
9
A




100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%

5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s

10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s

10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%

Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux

Hold 

time

Stand-by 

time 

Stand-by 

dimming level 

Daylight 

threshold

4. Functions

Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires 
a light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion 
hold-time and stand-by period; Selectable daylight threshold and freedom of detection area. 

4.1 Tri-level Control (Corridor Function)

The built-in daylight sensor can read ambient natural light and switch off the fixture automatically 
whenever artificial light is not required (natural light lux level exceeds daylight threshold). 
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light 
         is sufficient.

4.2 Lux Off Function

HIM35-20180525-A2

2. Installation 

Warnings: 

1. Installation of the sensor involves connecting it to the mains supply. This work must be 
    carried out by a specialist in accordance with electrotechnical regulations.
2. Disconnect power supply before installing.

The light will flash ONCE rapidly after receiving the command from the remote controller. 
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% 
or POWER 80% is pressed. 

4.3 Load Indication

5. Wiring Diagram

L
N
DALI 

+

DALI 

-

L
N

Brown

LED 

Driver

Blue

Red

Black

HIM35

A. Ceiling mount

B. Screw to the Luminaire by conduit 

C. Attach to the shade by clamp 

Sensor module

PIR

Daylight sensor

LED indicator

Infrared receiver

Rotary switch for programing

Cable entry

Installation rack

81.5

4.1

66.6

91.5

80.7

75

4.1

59.3

73.5

57.3

47.5

24.5

Cable entry

Sensor module

PIR

Daylight sensor

LED indicator

Infrared receiver

Rotary switch for programing

59.6

66.6

89.9

0.825”

75

64

43.8

43

59.3

73.5

35.2

57.3

47.5

Sensor module

PIR

Daylight sensor

LED indicator

Infrared receiver

Rotary switch for programing

Angle adjustment

Luminaire clamp 

53

66.6

80

146.6

75

64

18

50

84.5

47.5

59.3

Отзывы: