DISPLAY AND MENU OPTIONS
SETTING AC POWER LOSS GATE FUNCTION
The setting in the AC LOSS display determines what action the operator performs during an AC power
loss. The settings help reduce drain on the battery. You can choose between four settings depending
on customer preferences.
Table 10. AC Power Loss Menu
Menu Setting
Description
AP 0 AC LOSS
UPS FAIL OPEN
Normal gate functions continue until system detects battery voltage drop
below 21V. DEAD BATTERY appears on display and gate automatically opens.
Any pushbutton CLOSE command will close gate and any OPEN command
will re-open gate. If battery continues to diminish and system detects 18V
or less, system initiates an automatic open cycle. Any new open or close
command is ignored and LCD appears blank. System remains in this disabled
state until reset or battery recovers to 24V.
AP 1 AC LOSS
UPS FAIL CLOSE
Normal gate functions continue until system detects a battery voltage drop
below 21V. DEAD BATTERY appears on display and gate automatically closes.
Gate can be opened by a special sequence of a STOP input followed by an
OPEN push-button or directly opened with Fire Department Open command.
Any push-button CLOSE command closes gate. If battery continues to
diminish and system detects 18V or less, system initiates an automatic open
cycle if not already on a limit. Any new open or close command is ignored
and LCD appears blank. System remains in this disabled state until reset or
battery recovers to 24V.
AP 2 AC LOSS
AUTO OPEN
Operator automatically opens gate five seconds after AC power loss
detected. Gate remains open until AC power is restored. Any push-button
CLOSE command will close gate and any open command will open gate.
When battery voltage drops below 21V or less, system initiates an automatic
open cycle. Gate will remain open until battery recovers to 24V.
AP 3 AC LOSS
NO CLOSE TIMER
Operator initially does nothing after it detects AC power loss until it receives
an open command. Once an open command is received, operator opens
and remains in that state. Any push-button CLOSE command will close gate
and any open command will open gate. When battery voltage drops below
21V or less, system initiates an automatic open cycle. Gate will remain open
until battery recovers to 24V.
To designate what you want operator to do during
an AC power loss, access User Menu (see
Menu" on page 59 and Figure 36) and scroll
through items until AP (AC LOSS) display appears:
1.
Use SELECT and NEXT buttons to navigate
and change number on display. Review "Using
the Smart DC Controller Buttons In Menu
2.
To exit User Menu, press MENU button. A gate
status appears in display indicating you have
returned to Run Mode.
Figure 36. AC Power Loss
AP 0 (AC LOSS)
UPS FAIL OPEN
OPEN
CLOSE
STOP
MENU
RESET
PREV
NEXT
SELECT
61
| www.hysecurity.com
SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL
MX3640-01 REV. D ©2018
Содержание SwingSmart DC 20
Страница 2: ...2 www hysecurity com SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL MX3640 01 REV D 2018...
Страница 24: ...SAFETY INFORMATION 24 www hysecurity com SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL MX3640 01 REV D 2018...
Страница 138: ...NOTES 138 www hysecurity com SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL MX3640 01 REV D 2018...
Страница 139: ...NOTES 139 www hysecurity com SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL MX3640 01 REV D 2018...