26
© 2012 Installation and Reference Manual D0125 Rev. H
Section 3
—Installer Menu Functions
The Installer Menu is accessed by entering the User Menu first [
], and then pressing the RESET button and the
OPEN button simultaneously. The display reverts to the usage class [
] which is the first menu item in the Installer
Menu.
Installer Menu Options
Default
Description
I1
[uC 0] Set UL Usage Class
0
0 = gate disabled, Set Class 1 through 4 use
I2
[Sh 0] Set Handing of gate
0
0 = gate disabled, r = Right Hand, L = Left Hand
I3
[Fd 0] Load Factory Defaults
0
0 = User settings, 1 = Load defaults (resets full menu)
I4
[bu 0] Choose Buzzer
0
0 = Buzzer not set, 1 = Freq 1, 2 = Freq. 2
I5
[dg 0] Set dual gate type
0
0 = solo operator, 1 = Slave, 2 = Master, 3 = SallyPortA, 4 = SallyPortB
I6
[SG 0] Set sequential gate
0
0 = not active, 1 = Loop layout #1, 2 = Loop Layout #2
I7
[Ch 0] Set AC Charger or Solar
0
0 = DC + AC charger 1 = DC + Solar charger
I8
[Fo 0] Enable Fire Dept. Open
0
0 = disabled, 1 = enabled
I9
[oC 0] Enable Emergency close
0
0 = disabled, 1 = enabled (EFO model only)
I10
[SE 3] Inherent Sensor
3
1 = maximum sensitivity, 9 = Lowest sensitivity
I11
[SS 0] Inherent Sensor function
0
1 = stop only (note, functions in usage class 4 only)
I12
[LC 0] Leaf delay Close
0
0 = none (1-7) ½ second steps (Master/Slave only)
I13
[Lo 0] Leaf delay Open
0
0 = none (1-7) ½ second steps (Master/Slave only)
I14
[rt 0] Maximum run timer
0
0 = 60 Seconds max run, 1 = 300 Seconds max run
I15
[Po 0] Partial Open distance
0
0 = none, or 7 – 99 seconds
I16
[EC 0] PEC reverse to open
0
0 = Close eye stops only, 1 = 2 sec reverse to open
I17
[EO 0] PEO reverse to close
0
0 = Open eye stops only, 1 = 2 sec reverse to close
I18
[gr 0] Edge reverse to open
0
0 = Edge reverses fully open, 1 = 2 sec reversal only
I19
[Sr 1] IES reverse to open
1
0 = IES reverses fully open, 1 = 2 sec reversal only
I20
[PC 0] Set PEO/ PEC – NO/NC
0
0 = Normally Open PE output, 1 = N.C. (supervised)
I21
[gC 0] Set Edge input – NO/NC
0
0 = Normally Open Edge output, 1 = Normally Closed
I22
[tC 1] Time clock/ Interlock input
1
0 = select Time Clock, 1 = select Open Interlock
I23
[dt 0] Disable Free Exit/Close Tmr
0
0 = disable Free Exit, 1 = disable Close Timer
I24
[or 1] OOLD detector function
1
0 = pause closing only, 1 = enable reversing to open
I25
[ir 1] IOLD detector function
1
0 = pause closing only, 1 = enable reversing to open
I26
[dL 1] Vehicle detector logic
1
1 = std, 2 & 3 = quick close, 4 = full anti-tailgate*
I27
[r1 0] User relay 1 option
1
0 = disabled, 1 – 24 = see output options page 30
I28
[r2 0] User relay 2 option
6
0 = disabled, 1 – 24 = see output options page 30
I29
[r3 0] User relay 3 option
1
0 = disabled, 1 – 24 = see output options page 30
I30
[t L 0] Gate Open alert
2
0 = 0 sec, 1=15s, 2=45s, 3=75s, 4=105s, 5=135s
I31
[Lt 0] Loitering alert
3
0 = 0 sec, 1=15s, 2=45s, 3=75s, 4=105s, 5=135s
I32
[SA 0] System Address
0
0 = Off, 1-99 = Network “Drop” Address (RS-485)
I33
[ELd0] Test factory ELD*
0
0 = Run mode, 1 = show freq, 2 = show call level 0-7
I34
[iLd0] Test factory IOLD*
0
0 = Run mode, 1 = show freq, 2 = show call level 0-7
I35
[oLd0] Test factory OOLD*
0
0 = Run mode, 1 = show freq, 2 = show call level 0-7
I36
[SLd0] Test factory SLD*
0
0 = Run mode, 1 = show freq, 2 = show call level 0-7
*See page 44 for description of Vehicle Detector & Loop Fault diagnostics
If you wish to restore the factory default settings, go to menu item [
] and change the setting to 1, then press
the PROGRAM button. The entire menu will reset to the factory defaults. You will need to reprogram the operator
if you want it to recognize any settings other than its factory defaults.
These Notes Refer to the chart above:
I1, I2, I3a These settings must be configured before the gate operator can function. Once set, the User and Installer
Menu items become accessible as well
I3a The Option bu=0 only appears if the Controller has been reset to factory default settings
I5 These settings appear only if the factory has provided a DC powered gate operator
I9 IES stop only setting [SS __] does not appear unless set as a class 4 operator
I10, I11 These settings appear only if the Installer Menu is set for Master / Slave function
I27, I28 These settings appear only if the Installer Menu has set relays r1-r3 for these alerts
Содержание SlideDriver 50VF2
Страница 2: ......
Страница 28: ...14 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Страница 29: ...15 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Страница 36: ...22 2012 Installation and Reference Manual D0125 Rev H Section 3 Wiring Control Inputs...
Страница 54: ...40 2012 Installation and Reference Manual D0125 Rev H Section 5 Detector Loop Installation continued...
Страница 63: ...49 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Страница 64: ...50 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Страница 80: ...67 2012 Installation and Reference Manual D0125 Rev H Appendix 50VF2 3 Control Box STC and Component Wiring...
Страница 81: ...68 2012 Installation and Reference Manual D0125 Rev H...