background image

EN

English – 

5

4.5 - Initial start-up and electrical connections

After powering up the control unit, perform the following checks:

After a few seconds, make sure that the “Bluebus” LED (

fig. 16

) flashes regu-

larly with a frequency of about one flash per second.

Make sure that the LEDs on the photocells (

fig. 16

) flash (both on TX and RX).

The type of flashing is not important during this stage.

Make sure that the flashing light connected to the FLASH output is off.

If the above conditions are not satisfied, switch off the power supply to the con-
trol unit and check the electrical connections previously made.

4.6 - Learning of the devices connected

After the initial power-up, the control unit must be able to recognise the devices
connected to the “

Bluebus

” and “

Stop

” inputs.

IMPORTANT! 

– The learning procedure must be performed even if no

device is connected to the control unit.

The control unit is able to recognise the various connected devices individually
through the self-learning procedure and detect possible faults. For this reason it
is necessary to perform self-learning every time a new device is added or an
existing device is removed.
To indicate when the self-learning procedure is required, LEDs 

L1

and 

L2

on

the control unit (

fig. 16

) emit a number of slow flashes:

01.

Press and hold down 

and “

Set

” keys at the same time (

fig. 16

).

02.

Release the keys when LEDs L1 and L2 start flashing quickly (after approx.
3 seconds).

03.

Wait a few seconds for the control unit to complete the device learning
phase.

04.

At the end of this phase, the “Stop” LED must be lit and LEDs “L1” and
“L2” must be turned off (LEDs L3 and L4 may start flashing).

4.7 - Mechanical limiter position learning

After learning the connected devices (paragraph 4.6), the positions of the
mechanical stops must also be learnt (maximum opening and maximum clos-
ing). There are three ways to perform this procedure: 

automatic, manual 

and

combined.

In automatic mode, the control unit learns the positions of the mechanical stops
and calculates the most suitable offset value for the leafs (SA and SC, 

fig. C

).

In manual mode, the eight positions of the mechanical stops (

fig. C

) are pro-

grammed one by one, moving the leafs to the required points. The position to
program is identifiable by the flashing status of one of the eight leds (L1-L8), see

Table 2

.

In combined mode, the automatic procedure can be performed and then, using
the manual procedure, one or more positions may be modified, with the excep-
tion of positions “

0

” and “

1

” (

fig. C

) which coincide with the positions of the

mechanical stops.

4.7.1 - Learning in automatic mode
01.

Press and hold keys “

Set

” and “

” at the same time.

02.

Release the keys when leds “

L3

” and “

L4

” start flashing quickly (after

approx. 3 seconds).

03.

Ensure that the automation completes the following sequences of ma -
noeuvres:

a -

Low speed closure of gearmotor M1 through to the mechanical stop

b -

Low speed closure of gearmotor M2 through to the mechanical stop

c -

low speed opening of gearmotor M2 and gearmotor M1 through to the

mechanical stop

d -

High speed closure of gearmotors M1 and M2

Warnings:

– If the first manoeuvre (

a

) does not close the leaf controlled by motor M1 but

closes the one controlled by M2, press key “

” or “

” to stop the learning

phase. At this point, invert the connections of motors M1 and M2 on the ter-
minals on the control unit and then those of the respective encoders; after
this start the procedure from point 01;

– If the first two manoeuvres (

a

and

b

) are not “closing” but are “opening”,

press key “

” or “

” to stop the learning phase. At this point, on the gear-

motor that completed the opening manoeuvre, invert the polarity of the two
wires of gearmotor M1 (terminals 7 and 9) and of M2 (terminals 10 and 12)
and then start the procedure from point 

01

;

04.

At the end of the Closing manoeuvre of the 2 motors (

d

), leds “

L3

” and “

L4

turn off to indicate the that the procedure has been completed correctly.

Warnings:

– During the automatic learning procedure, if a photocell trips or a device con-

nected to the “stop” input is activated, the procedure is interrupted and led
L1 starts flashing. To resume the learning process, the procedure must be
started again from point 

01

;

– The automatic learning procedure can be repeated at any time, also after

installation; for example following modifications to the position of the
mechanical stops.

4.7.2 - Learning in manual mode
Caution!

– 

From step 03 onwards:

– to move from led L1 to L8, briefly press key 

or 

(the led flashes to indi-

cate the current position);

– to move the motor in one or the other direction, press and hold key 

or 

.

B

TABLE 2

PHOTOCELL ADDRESSES

Photocell

Jumpers

FOTO

External photocell h = 50 with trip on 
closure (stops and inverts movement)

FOTO II

External photocell h = 100 with trip on closure 
(stops and inverts movement)

FOTO 1

Internal photocell h = 50 with trip on closure 
(stops and inverts movement) and opening 
(stops and restarts when photocell is disengaged)

FOTO 1 II

Internal photocell h = 100 with trip on closure 
(stops and inverts movement) and opening 
(stops and restarts when photocell is disengaged)

FOTO 2

Internal photocell with trip on opening 
(stops and inverts movement))

FOTO 2 II

Internal photocell with trip on opening 
(stops and inverts movement)

FOTO 3
CONFIGURATION NOT ADMITTED

TABLE 2

Position

Led

Description

Position 0
(motor 1)

Position 0
(motor 2)

Position SA
(motor 2)

Position A
(motor 1)

Position A
(motor 2)

Position SC
(motor 1)

Position 1
(motor 1)

Position 1
(motor 2)

Maximum closing position: when leaf 1 reaches closing
mechanical stop

Maximum closing position: when leaf 2 reaches closing
mechanical stop

Opening offset: when leaf 2 passes this position the opening
of leaf 1 begins

Desired opening position: position at which the leaf connected
to motor 1 must stop at the end of an opening manoeuvre.
This position does not need to coincide with the opening
mechanical stop but can be chosen as desired between the
positions 0 and 1

Desired opening position: position at which the leaf connected
to motor 2 must stop at the end of an opening manoeuvre.
This position does not need to coincide with the opening
mechanical stop but can be chosen as desired between the
positions 0 and 1

Closing offset: when leaf 1 reaches this position, leaf 2 begins
to close

Maximum opening position: when leaf 1 reaches the opening
mechanical stop

Maximum opening position: when leaf 2 reaches the opening
mechanical stop

L1

L2

L3

L4

L5

L6

L7

L8

0

1

1

A

SC

SA

A

0

M1

M2

C

POSITIONS

Содержание HK7024

Страница 1: ...tions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalación y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise PL Instrukcje i ostrzeżenia do instalacji i użytkowania NL Aanwijzingen en aanbevelingen voor installatie en gebruik Swing gate opener HK7024 HK7224 ...

Страница 2: ......

Страница 3: ...r supervision to ensure that they do not play with it Do not allow children to play with the fixed control devices Keep remote con trol devices out of the reach of children WARNINGS AND GENERAL PRECAUTIONS 1 Contents 1 WARNINGS AND GENERAL PRECAUTIONS 1 1 1 Safety warnings 1 1 2 Installation warnings 1 1 3 Operation warnings 1 2 PRODUCT DESCRIPTION AND INTENDED USE 1 3 INSTALLATION 2 3 1 Prelimina...

Страница 4: ...e that the resist ance to movement is constant at all points of travel there should not be any points where more force or less is required Bring the gate leaves manually into a position at random then let go and check that they remain stationary Check that the gearmotor fixing zone is compatible with its overall dimen sions fig 1 Check that the place where the gearmotor is to be installed allows e...

Страница 5: ...5 50 B A 100 150 200 250 300 350 400 450 90 95 95 100 100 105 105 110 90 95 95 105 GRAPH 2 rotation fulcrum and the column surface designated for fixture of the rear gearmotor bracket b On Graph 2 note the obtained value B and from this point trace a hor izontal line until it intersects the area covering the range 90 95 c At the points of intersection between the horizontal line and the area trace...

Страница 6: ...ith other func tions see TABLE 3 Level 1 functions or via the Oview programmer see paragraph 8 3 ELECTRICAL CONNECTIONS 4 4 1 Electrical connections of gearmotor with control unit mod HK7024 Caution Only make the electrical connections after installing the gear motor WARNINGS Connections must be made exclusively by qualified personnel All electrical connections must be made with the unit disconnec...

Страница 7: ... the leaf controlled by motor M1 but closes the one controlled by M2 press key or to stop the learning phase At this point invert the connections of motors M1 and M2 on the ter minals on the control unit and then those of the respective encoders after this start the procedure from point 01 If the first two manoeuvres a and b are not closing but are opening press key or to stop the learning phase A...

Страница 8: ... the control unit per form a few opening and closing manoeuvres to ensure that the gate moves cor rectly and to check for installation or setting defects 01 Press the Open key Check for the correct leaf opening offset and check that the opening manoeuvre includes the acceleration constant speed and deceleration phases and that the leaf limit switch is set a few centime tres from the opening mechan...

Страница 9: ...c closure is activated with the programmed pause time Function ACTIVE in the event of a power failure even of short duration when power is restored the con trol unit detects gate open and automatically starts a closure manoeuvre preceded by 5 seconds of pre flashing Function NOT ACTIVE when power is restored the gate remains where it is Function ACTIVE after 1 minute from the end of the manoeuvre ...

Страница 10: ...2 L3 L4 L5 L6 L7 L8 Very slow Slow Medium Fast Very fast Extremely fast Fast opening Slow Closing Extremely fast Opening Medium Closing Sets the motor speed during normal travel Motor speed L6 L1 L2 L3 L4 L5 L6 L7 L8 Pedestrian 1 opening of leaf M2 to 1 4 of total opening Pedestrian 1 opening of leaf M2 to 1 2 of total opening Pedestrian 3 opening of leaf M2 to 3 4 of total opening Pedestrian 4 Co...

Страница 11: ... lamp connected to the S C A open gate light output when this output is programmed as Mainte nance light The various warning lamp signals are shown in Table 7 To program the limit value of the maintenance operations see Table 5 Some devices are able to emit signals that serve to recognise their state of operation or possible faults If a flashing light is connected to the FLASH output on the contro...

Страница 12: ...ashes Error on internal parameters in control unit Wait at least 30 seconds then try giving a command and if necessary turn off the power supply If the condition persists there may be a malfunction and the electronic board must be replaced 6 short flashes 1 second pause 6 short flashes Maximum limit of consecutive mano euvres or manoeuvres per hour excee ded Wait a few minutes until the manoeuvre ...

Страница 13: ...nnecting the solar power system Solemyo CAUTION When the automation is powered by the Solemyo system IT MUST NEVER BE POWERED simultaneously by the electrical mains For more information on the Solemyo system refer to the relative instruction manual To connect the Solemyo system proceed as shown in fig 20 8 5 Connecting the external release system Kio CAUTION Kio must be connected to the gearmotor ...

Страница 14: ...ions and the results of tests performed on prototypes As it is only an estimation it does not represent any form of guarantee on the effective lifetime of the product Example of calculating the lifetime of a HYKE gearmotor with LONG length arm refer to Table 13 and Graph 3 leaf length 2 8 m severity index 20 leaf weight 230 Kg m severity index 20 solid leaf severity index 15 Total severity index 5...

Страница 15: ...on for buffer battery PS124 Solar power provision for SYKCE kit Maximum absorbed power 300 W 140 W Maximum absorbed current 1 5 A 3 A for version HK7024K V1 6 A for a maximum interval of 2 s Absorbed power with All Standby 1 function when powered by PS124 less than 100 mW or SYKCE kit including OXI receiver Flashing light output one LUCYB flashing light 12 V 21 W bulb Electric lock output one 12 V...

Страница 16: ...5 December 2004 regarding the approximation of member state legis lation related to electromagnetic compatibility repealing directive 89 336 EEC according to the following standards EN 61000 6 2 2005 EN 61000 6 3 2007 The product also complies with the following directives according to the requirements envisaged for quasi machinery Directive 2006 42 EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of 17 ...

Страница 17: ...al documentation Images IT Documentazione Tecnica Immagini FR Documentation Technique Images ES Documentación Técnica Imágenes DE echnische Dokumentation Bilder PL Dokumentacja Techniczna Zdjęcia NL Technische documentatie Afbeeldingen ...

Страница 18: ...ion it is not a game The product is not intended for use by persons including children with limit ed physical sensory or mental capacities or who lack experience or knowl edge unless supervised or trained in the use of the product by a person responsible for their safety Faults if an operating fault is detected in the automation system cut off the electricity supply to the automation system and re...

Страница 19: ...e in prossimità dell automazione e non lasciare i telecomandi alla loro por tata per evitare attivazioni involontarie non è un gioco Il prodotto non è destinato ad essere utilizzato da persone bambini compresi le cui capacità fisiche sensoriali o mentali siano ridotte oppure con mancanza di esperienza o di conoscenza a meno che esse abbiano potuto beneficiare attraverso l intermediazione di una pe...

Страница 20: ...st toutefois prudent d inter dire aux enfants de jouer à proximité de l automatisation et de ne pas laisser les télécommandes à leur portée afin d éviter des activations involontaires ce n est pas un jeu Le produit n est pas destiné à être utilisé par des personnes enfants compris dont les capacités physiques sensorielles ou mentales sont réduites ou man quant d expérience ou de connaissance à moi...

Страница 21: ... todos modos conviene impedir que los niños jueguen cerca del automatismo y mantener los mandos a distancia fuera de su alcance para evitar activaciones involuntarias no es un juguete El producto no está destinado a su uso por parte de personas niños inclui dos cuyas capacidades físicas sensoriales o mentales se hallen disminuidas o que carezcan de la experiencia o conocimientos necesarios a no se...

Страница 22: ...d die Flügel stillstehen Wenn sich das das Tor oder die Eingangstür schließt ist das Durch queren STRIKT VERBOTEN Den einwandfreien Betrieb der Fotozellen regelmäßig prüfen Kinder eine Automatisierungsanlage gewährt einen hohen Sicherheitsgrad mit ihrem Erfassungssystem kontrolliert und garantiert sie ihre Bewegung in Anwesenheit von Personen oder Gegenständen Als Vorsichtsmaßnahme soll ten Kinder...

Страница 23: ...oki poziom bezpieczeństwa a niezawod ne fotokomórki uniemożliwiają wykonanie ruchu w obecności osób lub rzeczy Mimo to lepiej zabronić dzieciom bawienia się w pobliżu automatyki oraz nie zostawiać nigdy pilotów bez nadzoru aby uniknąć nieumyślnej aktywacji urzą dzenia to nie zabawka Produkt nie może być użytkowany przez osoby w tym dzieci o ogranicze niach fizycznych lub umysłowych a także przez t...

Страница 24: ... terwijl het sluit Controleer de goede werking van de fotocellen regelmatig Kinderen een automatisering garandeert een hoge veiligheidsgraad Door haar detectiesystemen controleert en belet ze de beweging ervan in aanwezig heid van personen of voorwerpen Het is echter verstandig kinderen te verbie den in de buurt van de automatisering te spelen en de afstandbedieningen bui ten hun bereik te houden ...

Страница 25: ...IX 1 2 3 4 320 mm 210 mm 290 mm ...

Страница 26: ...X 1 3 2 5 7 6 0 150 175 200 225 250 275 300 325 350 375 400 425 450 475 50 B A 100 150 200 250 300 350 400 450 90 95 95 100 100 105 105 110 90 95 95 105 8 ...

Страница 27: ...XI 1 2 a b 3 9 5 OK OK b a 9 b a a b x 4 c a 4 1 2 3 4 90 90 10 7 6 8 ...

Страница 28: ...XII 9 1 2 a b 3 10 5 b x 4 c a 4 8 b a 10 1 2 3 13 11 6 OK OK 7 ...

Страница 29: ...XIII 1 2 90 3 90 12 A 90 2 1 3 12 B 4 OK 3 NO 2 NO 11 1 3 2 5 4 ...

Страница 30: ...FLASH ELS S C A OPEN CLOSE BLUEBUS TX 24V 4W RX P P NC NO C C NO NC STOP P P STOP 24 Vcc 13 1 2 14 1 2 5 1 2 3 4 XIV ...

Страница 31: ...6 1 2 8 7 15 1 3 5 1 2 2 4 XV ...

Страница 32: ...XVI 16 1 2 7 6 17 L1 OPEN STOP CLOSE L2 L3 L4 L5 L6 L7 L8 ...

Страница 33: ...XVII 1 2 1 2 18 1 3 5 1 2 2 2 1 4 19 1 2 ...

Страница 34: ...XVIII 1 2 20 1 4 1 2 3 2 ...

Страница 35: ...XIX 21 1 3 5 1 2 2 4 6 2 1 3 7 ...

Страница 36: ... Buchelay France Ph 33 0 1 30 33 95 95 Fax 33 0 1 30 33 95 96 info fr niceforyou com Nice France Sud Aubagne France Ph 33 0 4 42 62 42 52 Fax 33 0 4 42 62 42 50 infomarseille fr niceforyou com Nice France Rhône Alpes Decines Charpieu France Ph 33 0 4 78 26 56 53 Fax 33 0 4 78 26 57 53 infolyon fr niceforyou com Nice Belgium Leuven Heverlee Belgium Ph 32 0 16 38 69 00 Fax 32 0 16 38 69 01 info be n...

Отзывы: