Page 51
13.3.1 Changing the set point humi-
dity
The set point humidity may only be changed
if „PI controller“ was selected as the control
mode.
»
Select the "Humidity_set value [%]"
screen using or .
»
Tap on the Humidity_set value dis-
play.
»
Enter the value of the intended
humidity set value using the on-
screen keyboard which has opened.
»
Confirm the input and save using the
check mark in the top right, cancel
using the "X" in the top left.
Table of the read values available in the main screen and the humidity set value
(only when PI-controller was selected)
Mainscreen
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
Min
Max
FS
[ ] refers to a related explanation of the term
Pressure_acutal_value
The current system pressure in the unit in bar
Pressure_set_value
The set point of the system pressure in bar
Frequency_set_value
The frequency set value for the frequency inverter
Load_actual
The current load range of the system at the time of reading.
Humidity_actual_value
Actual value [1] of rel. humidity [2] in %
Humidity_set_value
0,0
99,0
50,0
Set value [3] of RH [2] in %
Demand
The demand [5] is the control signal from which the internal actuator signal [42] is
created
Control_sig._internal
Internal actuator signal [42] as a percentage of the actuator signal for the nominal
output
Humidity_set_max
5,0
99,0
80,0
Specification of max. humidity for the switch-off point when using the floating
max. limiter [35]
Adjustment/value range
Factory setting (FS) Bold
Read value
Read value
Read value
Read value
Read value
Read value
Read value