  © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were  

current as of document revision date and are subject to change without notice. 

|

  Part No. HY-2019016

SAPPHIRE COMPACT FIXED FIRE SUPPRESSION SYSTEM 

INSTALLATION GUIDE

2019-OCT-07    REV. 00   PAGE 1

INTRODUCTION

Small enclosures, detailed within this document include the 

following examples:
•   Electrical enclosures (distribution, control, and  

communication)

•  CNC machines
•  Wind turbine electrical cabinets 
Such enclosures can present a particular problem where 

faulty equipment and/or damaged wiring increase the risk 

of a fire. Other applications that fall within the system certifi-

cation criteria can be considered for protection. 
It can be difficult to identify when there is a fire in an 

enclosed volume until it is too late to take action. This is the 

case in well sealed enclosures where there is limited egress 

of combustion products and heat from the enclosures. 
The HYGOOD® SAPPHIRE® COMPACT Fixed Fire 

Suppression System provides protection inside the 

enclosure and discharges at the heart of the fire, ensuring 

that it is suppressed.
An important characteristic of SAPPHIRE COMPACT 

systems is that they stop the migration of the fire from the 

enclosure where the fire starts to neighbouring enclosures, 

significantly reducing consequential losses and disruption.
The SAPPHIRE COMPACT Fixed Fire Suppression System 

is specifically designed to protect small enclosures in accor-

dance with LPS 1666 (Loss Prevention Standard) - Direct Low 

Pressure (DLP) Application Fixed Fire Suppression Systems 

using Heat Sensitive Pneumatic Detection Tube for the 

Protection of Small Defined Volume Unoccupied Enclosures.

PRINCIPLES OF OPERATION

Upon flame impingement or high ambient temperature, the 

pressurised detection tube, connected to a container holding 

the suppression agent, ruptures with a burst at the hottest 

point. The agent then discharges through the burst hole at 

the heart of the fire.
Each SAPPHIRE COMPACT Fixed Fire Suppression 

System can protect one of up to four enclosures, each 

up to 2 m

3

, with one system. Each enclosure may be 

multi-compartmental.

FIGURE 1

E000947

!

  

WARNING

Damage to the detection tube may lead to inadvertent 

system discharge.

SUPPRESSANT

The SAPPHIRE COMPACT systems detailed in this 

document are used with 3M™ Novec™1230 Fire Protection 

Fluid, an electrically non-conductive clean agent. A Material 

Safety Data Sheet is available upon request.
Novec 1230 fluid is applied as a gas but is a liquid at room 

temperature. It vapourises upon discharge due to its low 

vapourisation heat and has a larger heat capacity than air 

alone. Novec 1230 fluid absorbs enough heat to suppress 

the fire and requires the concentration of agent within 

the enclosure to be maintained for a sufficient duration. If 

discharged, it inflicts no damage to electronic equipment or 

the data stored on it. Novec 1230 fluid is an environmentally 

stable solution that does not damage the ozone layer.

VISUAL INSPECTIONS

The responsible person should carry out visual inspections 

of all SAPPHIRE COMPACT systems regularly. These 

visual inspections should be carried out at least once a 

month. Complete the following visual inspections:
•   The operating instructions of each system are clean and 

legible.

•   The valves on each system are open and have not been 

closed. Where the valve lever is in the vertical position 

on the standard valve and downwards on the monitored 

valve, the ball valve is open and the system is  

commissioned – see Figure 2.

Standard Valves  

(Part No. 302150006 and 302150007)

Valves with System Isolation Monitoring  

(Part No. 302150008 and 302150009)

FIGURE 2

E000973

•   Each system has not been operated and is not damaged 

or has any missing parts.

•   The reading of any pressure gauge or indicator fitted to a 

system is within the operational and safety limits (15 Barg) 

– see Figure 3.

•   The locking screw of each system is not broken or 

missing, where applicable – see Figure 4.

BALL VALVE OPEN

- SYSTEM  

COMMISSIONED

BALL VALVE CLOSED

- SYSTEM NOT  

COMMISSIONED

BALL VALVE OPEN

- SYSTEM  

COMMISSIONED

BALL VALVE CLOSED

- SYSTEM NOT  

COMMISSIONED