Setting a sinusoidal load
Besides the ramp, you can also program a sinusoidal load:
A
amplitude of
the oscillation and corresponds to the Volt value as a percentage of the maximum out-
put voltage.
O
Offset
between zero and the baseline of the oscillation and corresponds to the Volt value as a per-
centage of the maximum output voltage.
F
Frequency of
the oscillation - is given as a multiple of 10 mHz
Area
Value range
A
1…10V
O
1…10V
A+O
10V
F
0.01Hz...2Hz in 10nHz steps
A minimum offset of 10% [1V] is specified in this operating mode. The amplitude of the sine is added to the off-
set. The value of 100% [10V] is not exceeded, nor is the value falling below 0% [0V].
Make sure that the sum of
amplitude
and
offset
is less than 100% [10V].
A negative amplitude cannot be displayed.
Switch to configuration mode
ID
DLC
B0
B1
B2
B3
B4
B5
B6
B7
0x620
8
99h
01h
00
00
00
00
00
00
Select operating mode and define sine wave
ID
DLC
B0
B1
B2
B3
B4
B5
B6
B7
0x620
8
10h
xxh
yyh
yyh
zzh
zzh
vvh
vvh